    Research on resonance fault caused by dc magnetic biasing in ultrahigh voltage transformer with parallel static var compensator

    2020-10-15 02:04:28YangNanZhuZiminYuanTiejiang

    Yang Nan Zhu Zimin Yuan Tiejiang

    (1School of Electrical Engineering, Dalian University of Technology, Dalian 116024, China)(2School of Electrical Engineering, Xinjiang University of Technology, Urumqi 830046, China)(3Electric Power Research Institute, State Grid Xinjiang Electric Power Company, Urumqi 836500, China)

    Abstract:For dealing with the resonance fault of ultra-high voltage transformers (UHVTs) with the parallel thyristor controlled reactor (TCR)+ the filter compensator (FC) type static var compensator (SVC) caused by dc magnetic biasing, a simulation model of UHVT with parallel SVC for the frequency analysis of the impedance characteristics and a magnetic-field coupling model for UHVT based on classic Jiles-Atherton hysteresis theories are constructed based on the MATLAB/Simulink platform. Both the theoretical and simulation results prove that the resonance fault is caused by the resonance point on the low-voltage side of the transformer, which will approach the 4th harmonic point under magnetic biasing. Based on the fault analysis, a new resonance control method is proposed by adding reactance with by-pass switches in series with FC branches. Under dc magnetic biasing, the cutoff of the by-pass switch will increase the series reactance rate of the FC branches and change the resonance point. In order to avoid the 7th harmonic increasement caused by this method, the firing angle of the TCR branches is locked between 130° and 180°. The effect of the proposed method is validated by the simulation model of a 750 kV UHVT and the results show that the mechanism analysis of the resonance fault is correct and the resonance control method is valid.

    Key words:static var compensator; ultra-high voltage transformer; magnetic biasing; resonance fault

    With the rapid development of the large-scale ultra-high voltage cross-area interconnected power grid, the dynamic reactive power compensator such as static var compensator(SVC), which is commonly deployed in parallel to the power transformer, has been gradually applied to the power system. Due to the low direct-current resistance of the transmission line and frequent turbulence of the self-coupling transformer, dc magnetic bias current can be found in ultra-high voltage girds frequently[1]. When magnetic bias current flows through ultra-high voltage power transformers (UHVTs), an odd number harmonics current will be generated and cause potential resonance to the SVCs connected parallel to UHVTs. This abnormal operation of SVC can either cause a decrease in its reactive power supply ability or cause a complete shut-down of the device, which can further reduce system stability[23]. Therefore, necessary attention should be paid to this topic.

    Most research focused on studying the effect of magnetic bias current on the static power component such as transformers and reactive compensation capacitors (RCCs) connected to the transformer[46]. The influence of magnetic biasing on dynamic power compensators such as SVC is rarely discussed.

    In Ref.[7], the magnetic bias effect on the winding current of UHV is simulated with the edge finite element method. The result shows that the distortion of the winding current is directly linked to the magnetic biasing current. Harmonic amplification is very detrimental in this case. However, the research is only carried out with a resistive load and focuses only on the transformer itself.

    The ability of power transformers to withstand the dc bias is studied by a novel analytical method in Ref.[8]. The conclusion pointed out that the peak values of the exciting currents at the saturation conditions caused by the dc biasing and the overvoltage are directly linked. A magnetic biasing treatment plan is proposed in Ref.[9]. The authors developed a 3-port converter topology and utilized dc modulation magnetic flux for compensating for the dc bias problem.

    In Refs.[1011], the influence of bias current on the reactive power supply ability of the transformer was studied. Researchers pointed out that under magnetic biasing, the reactive power loss of the transformer will increase dramatically with the bias current, reducing its equivalent impedance. During this process, a large proportion of even number harmonics will be generated,significantly distorting the excitation current. If the reactive power compensator is still active in this case, the frequency characteristic of the impedance will be changed as well as its parallel resonance point. The resonance of even number harmonics may occur on the capacitor branch of the power compensator and be amplified under the magnetic biasing.

    In Ref.[12], Yang et al. pointed out that the resonance fault in RCC can be avoided by increasing the series reactance rate under the magnetic biasing. However, this method cannot be directly applied to SVC devices due to the strict high-order harmonic requirement.

    Refs.[1314] pointed out that the increase of reactive power loss caused by dc magnetic biasing on a specific node point in a UHVTS can reach 200 Mvar under strong magnetic storm conditions. Any resonance or amplification under such a condition is a dangerous threat to the grid. Without a proper control method, this can lead to a complete shutdown of the system.

    This paper focuses on the potential resonant and harmonic amplification problems of the UHVTs with TCR+FC type SVCs under the influence of dc magnetic bias current. The characteristics of the SVC are investigated, and the causes of the resonance and amplification of harmonics are explained. The corresponding control methods are proposed. MATLAB/Simulink models for simulating the characteristics of the ultra-high voltage transformer with parallel SVC(UHVT-PSVC) and magnetic coupling feature under dc magnetic biasing are constructed. The results of the simulation and the corresponding configurations of the control method are provided.

    1 Resonance Fault in UHVT with Parallel SVC under Magnetic Biasing

    1.1 Mechanism of resonance fault

    Static var compensator type TCR+FC consists of thyristor-controlled reactors (TCRs) and filter compensators (FCs). It is connected to the low-voltage side of the transformer as shown in Fig.1. In Fig.1,Inis the equivalent harmonic current source caused by dc magnetic biasing. Branches 1#,2#and 3#are the 3rd/5th/7th order FC branches for SVC. By converting the impedance of the high/medium side to the low-voltage side, the total equivalent impendence of the transformer node is calculated as

    Zsys=(Z′total//Z′Q)//ZSVC

    (1)

    Fig.1 Equivalent circuit of UHVT-PSVC with dc magnetic biasing on the low-voltage side

    Z′totalconsists of the resistances of the windings, leakage reactance and the excitation impedanceZmof the transformer. Winding resistances are negligible during the normal operation of the transformer. The reduction ofZmis the main reason for the increasing reactive power lossQdccaused by the saturation of the transformer under magnetic biasing. Therefore,Qdccan be treated as the reactive power load parallel to the primary side of the transformer. By converting to the low-voltage side, this loss is expressed by impedanceZ′Q. The impedance of SVC is composed of TCR branch impedanceZTCRand FC branch impedanceZFC. The mechanism of the resonance fault in the transformer under magnetic biasing is shown in Fig.2. The series reactance rate of the parallel capacitor branch is calculated asK=XL/XC.

    Fig.2 The mechanism of resonance fault in the transformer under magnetic biasing

    As the maximum value ofZSVChas its limitation, the presence ofZ′Qwill reduce the equivalent impedance of the transformer and increase the short-circuit capacity of the node. The order of the system parallel resonance point is also increased, which can be estimated by

    (2)

    whereQSVCis the reactive power of SVC;STis the short-circuit node capacity; andKis the series-reactance rate. Usually, the series-reactance rate of capacitors in the power system is assumed to be 12%-13% or 5%-6%(for the 3rd and 5th harmonics). However, due to the harmonic requirement, the series-reactance rate of the SVC is usually lower than these values. If the SVC only provides reactive power from capacitor branches and FC branches are tuned precisely to the 3rd,5th and 7th harmonics, the input impedance characteristics on the low-voltage side of a 750 kV transformer without magnetic biasing are shown in Fig.3 when FC branches are activated.

    Fig.3 Impedance characteristics on the low-voltage side of the transformer

    With the connection of 2 FC branches on the low-voltage side of the transformer, the 2nd parallel resonance point can be observed around 200 Hz as shown in Fig.3. The frequency of the resonance point will be reduced while the active number of FC branches increases. Combined with the results from Fig.2, it is fair to say that the change of equivalent impedance caused by dc magnetic biasing and the impedance characteristics of the SVC devices are two major reasons for the resonance faults. The 4th harmonic parallel resonance is most likely to occur when the FC branches are tuned to the 3rd, 5th and 7th harmonics and all 3 sets of FC branches are switched on. With the increase in the series-reactance rate, the possibility of parallel resonance with 2 FC branches will also be increased.

    By considering the possible harmonic amplification of the harmonic current in FC branches when SVC is activated, two operation methods of SVC can be categorized under magnetic biasing:

    1) Method 1. When active FC branches are just enough to compensate for the reactive power lossQdc, or the SVC reaches its maximum capability, the SVC can be treated as parallel capacitors. Assuming that only one FC branch 1#is switched on and the TCR branch remains off, by ignoring the small branch resistance, then-th harmonic reactance of the FC branch is calculated as

    (3)

    Since the SVC is in parallel with equivalent impedance on the system sideZTsys, then-th harmonic current on the 1#branch is calculated as

    (4)

    IfXFC1n<0, the amplitude of then-th harmonic in the FC branch of SVC device will be amplified, causing potential series-resonance with the leakage reactance on the system side.

    2) Method 2. If the SVC devices are sufficient to compensate for reactive power lossQdcand follow

    (5)

    The capacitive power compensated by SVC is now composed of two parts:QTCRandQFCi. In this mode, the harmonic current in the FC branch is calculated as

    (6)

    In this case, the connection of the TCR branches will enhance the absolute value of the system impedance, increasing the 5th and 7th harmonic content of the SVC device. Actions should be taken to reduce the effect of these harmonics.

    1.2 Resonance fault control procedure

    The analysis in Section 1.1 indicates that the system parallel resonance point can be altered by changing the series-reactance rateK. This can be used to prevent the potential harmonic amplification problem in FC branches. When configuring then-th harmonic series reactance of the FC-branch,Kshould follow the equation below:

    (7)

    If even number harmonics and their resonance points change under the magnetic biasing are taken into consideration,Kvalue must be set to be greater than 6.25%. This will keep the reactance of FC branches inductive in the 4th order harmonic[15]. However, by considering the potential frequency shift of system parallel resonance and equipment characteristics,Kshould be set to be 7% to prevent resonance and harmonic amplification under magnetic biasing.

    However, the rateKof the 7th order harmonic FC branch is only 2.04% in the theoretical calculation, which is insufficient for normal operation under magnetic biasing. To ensure that rateKsatisfies the requirement of both normal and magnetic biasing, an improved structure of FC branches is proposed as shown in Fig.4. By-pass switchK1is used to control the rateKof the SVC under both normal and magnetic biasing conditions. When switched off under magnetic biasing, rateKin the full branches can be increased to 7% (i.e. 7%=ω2L1+L2C). When switched on, the additional reactanceL1is short-circuited and rateKcan be restored to normal.

    Fig.4 An improved structure of the FC branch

    As mentioned in operation method 2, the activation of TCR branches will increase the impedance on the low-voltage side of the transformer. As the impedance of FC branches is also increased, the 5th and 7th harmonic content in the transformer should be properly controlled in this case. By setting the firing angle (α) of TCR between 130° and 180°, the corresponding change ofQTCRcan be limited below 0.25 p.u.. As the capacity of TCR is slightly greater than the sum of all FC branches in the SVC, TCR can provide 1/3 more inductive power than the sum of all reactive power provided by FC branches. It should cover the requirements in practical use. The resonance fault control procedure of a UHVT-PSVC under dc magnetic biasing is shown in Fig.5.

    2 Model Construction of a UHVT with Parallel SVC under Magnetic Biasing

    2.1 Equivalent circuit of a UHVT with parallel SVC

    Currently, most UHVTs applied to 500 kV and the above voltage rate are single-phase self-coupling transformers. The system is 3-phase balanced during normal operations and the impedance change in each phase is almost identical. Therefore, a single-phase UHVT-PSVC simulation model for impedance/frequency analysis is constructed based on MATLAB/Simulink as shown in Fig.6.

    Fig.5 Resonance fault control procedure for UHVT-PSVC under dc magnetic biasing

    Fig.6 The equivalent circuit model of a single-phase UHVT-PSVC

    No single-phase self-coupling transformer is available in MATLAB/Simulink. Therefore, the ideal single-phase 3-column transformer, whose primary side is connected to its secondary side, is used as a substitution. As shown in Fig.6, the “Priminal” is the primary side of the transformer, and “Secondary” is the medium-voltage side of the transformer. SVC is connected to the low-voltage side of the transformer through single-phase transmission lines.

    Block impedance vs. frequency uses a harmonic current source with parallel resistance as the harmonic voltage source. The impedance/frequency characteristics of the 2-terminal time-invariant system are obtained by calculatingX=Uz(s)/Iz(s). The data is then transported to the Impedance vs. Frequency Measurement program in powergui block to acquire the impedance/frequency characteristics.

    The winding settings of ODFPS-500000/750 UHVT-PSVC are shown in Tab.1. The total compensation capacity of SVC devices is 180 Mvar and the series-resistance in the FC-branch of SVC is 0.08 Ω. When TCR is not switched on, the series-reactance rates of 3 branches are 12%,6% and 6%. The input impedance characteristics and impedance angles with different FC branches are shown in Fig.7.

    Tab.1 Winding parameters of ODFPS-500000/750 single-phase self-coupling transformer

    Compared with Fig.3, it is obvious that the change ofKis very important for the input impedance characteristics. With the connection of FC branch 2#and 3#, both amplitude and the frequency range of the parallel system resonance, especially those around 4th harmonic, are significantly reduced. The capacitive range of system impedance is also reduced as analysed previously.

    Fig.7 Impedance characteristics on the low-voltage side of the transformer

    2.2 Magnetic coupling model of the transformer under magnetic biasing

    Self-coupling transformer ODFPS-500000/750 adopts a single-phase four-column structure. Both main columns are equipped with low-medium-high voltage windings. The excitation current on each column isi0/2. By ignoring the influence of low-voltage windings under no-load conditions, the equivalent circuit model of each column is shown in Fig.8. The key parameters are shown in Tab.2.

    Fig.8 The equivalent circuit of one column in a single-phase four-column self-coupling transformer

    Tab.2 Key parameters of a 750 kV single-phase self-coupling transformer

    The mathematical model of the single-phase self-coupling transformer is

    (8)

    whereU′1+(-U2)=U1U′1+(-U2)=U1;i1+i2=i2i1+i′2=i2;λσ11,λσ22are the leakage permeances of each winding;N1andN2are the number of turns in each winding;λis the main permeance. According to the classic Jiles-Atherton hysteresis model[16], we have

    (9)

    whereHis the magnetic field strength;Mis the magnetization intensity;Manis the anhysteretic magnetization intensity of the typical magnetic material, and it is calculated as

    (10)

    δ=sgn(dH/dt) is the directional coefficient;Ms,a,α,crepresent the characteristics of the iron core material, which are defined in Ref.[17];km=k(1-0.96(M/Ms)2) is the dynamic modification value ofkin Ref.[18]. The instant main permeance of the iron core can be calculated byλ=SμFe/lλ=SμFe/l, whileμFe=μ0(1+dM/dH)μFe=μ0(1+dM/dH) is the permeability of the iron core,Sis the cross-section area of the iron core andlis the length of the equivalent magnetic path.

    By programming Eqs.(9) and (10) into the S-function blocks of Simulink software, the magnetic coupling model of the transformer is shown in Fig.9. The parameters of the highly-conductive cold-rolled silicon-steel sheet 57ZH100 used in the ODFPS-500000/750 transformer is obtained from Ref.[19] (Ms=1.68 MA/m,k=10.918 9,c=0.3,α=13.9×10-6,a=8). Through simulations, theB-Hcurve andi0-μFecurves of the transformer’s iron core under the no-load condition are shown in Fig.10.

    The rated flux densityBand peak value of magnetic field strengthHare 1.67 T and 39.58 A/m, respectively. According to the no-load current ratio (0.05%), the rated excitation current of the transformer is 0.7 A. Compared with Fig.10, theB-Hcurve and the peak value of the excitation current calculated from the simulationB-Hcurve matches the results on the manuscript of the transformer. The relative error of the rated excitation current is only 7.86% (The rated excitation current of the transformer is 0.645A on the manuscript). The reactive power loss of the transformer can be calculated as[20]

    Fig.9 Simulation model of the transformer under dc magnetic biasing

    ΔQ=IbU1

    (11)

    whereIbis the RMS value of the fundamental positive sequence component in the reactive component of the excitation current. Throughout the model simulation and Fourier analysis, it is set to be 0.278 5 A. Therefore, the no-load loss of the transformer is calculated as 0.120 6 Mvar, only 0.5% difference from the 120 kW no-load experimental result. These comparisons show that the simulation model is accurate.In the worst-case scenario (i.e. when the maximum magnetic biasing current is 145.95 A), the single-phase self-coupling reactive power lossQdcis shown in Tab.3.

    Tab.3 Reactive power loss of a single-phase self-coupling transformer versus DC magnetic biasing current

    (a)

    WhenIdc=122.67 A,Qdcreaches the maximum capacity of SVC, andXtis reduced to 61.48% of the rated value. IfIdcis further increased to 145.95 A,Xtwill decrease to 57.29%. By the data fitting ofIdc,XtandQdc, the approximate relationship is expressed as

    Xt≈-0.00 2806Idc+0.952 5≈
    -0.001 837Qdc+0.952 5

    (12)

    Following the analysis above,the relationships among the equivalent impedance of transformerXt, magnetic current and reactive power loss are simulated to be linear as shown in Fig.11. Therefore,Xtis used to evaluate the magnetic biasing condition in this paper instead ofIdcandQdc.

    Fig.11 Relationships among the equivalent impedance of transformer Xt, magnetic current and reactive power loss

    3 Simulation of a 750 kV UHVT with Parallel SVC under Magnetic Bias

    3.1 The impedance/frequency characteristics of a UHVT with parallel SVC system

    The 750 kV three-phase UHVT-PSVC (type TCR+FC) described in Section 2 is applied in this simulation. When the series-reactance rate is increased to 12%,6% and 6%, the effect of the dc magnetic biasing on the input impedance on the low-voltage side of the transformer is simulated in this section.

    1) Method 1. While TCR is switched off, the frequency/impedance characteristics on the low-voltage side of the transformer are analyzed in Tab.4. Four classic data sets are categorized into 2 groups (with different FC branches turned on) and simulated correspondingly. The value and angle of input impedances on the low-voltage side of the transformer under different magnetic biasing currents are shown in Figs.12 to 14.

    Tab.4 The reactive power loss of a single-phase self-coupling transformer versus dc magnetic biasing current

    (a)

    (a)

    (a)

    With the increase in magnetic biasing current and the activation of 2 FC branches, the 2nd resonance point occurs around 185 Hz. The impedance under the 4th harmonic condition is proved to be capacitive. With the decrease in the transformer’s equivalent impedance, both the frequency and amplitude of the parallel system resonance point change drastically. WhenXt=74.84%, the peak value of impedance in 187 Hz is 1.79 times that of 78.52%.

    With the further increase in magnetic biasing current, the equivalent impedance of the transformer keeps decreasing. The third FC branch is switched on to compensate for the reactive power loss caused by magnetic biasing. The input impedance value and the impedance angle with 3 FC branches are shown in Fig.13.

    By comparing Fig.12 with Fig.13, it is observed that the 2nd parallel resonance point with 2 FC branches is closer to the 4th harmonic. With the connection of the 3rd FC branch, the saturation level of the iron core in the transformer keeps rising, which causes the system parallel resonance points to fluctuate between the 3rd and 4th harmonics. The peak impedance value of the resonance point is decreased as well as the capacitive area of the impedance angle. WhenXt=57.29%, the system parallel resonance points are located between 134 and 177 Hz. The 4th harmonic impedance value is increased.

    2) Method 2. The simulation result of Method 2 is analyzed in Fig.13. In this simulation, 3 FC branches are switched on while the equivalent impedance of the transformer is set to be 57.29%. When TCR branches are switched on and provide 60/90 Mvar reactive power for the system, the total power provided by the SVC is 120 and 90 Mvar. The impedance/frequency characteristics under these 2 situations are simulated as shown in Fig.14.

    When 90 Mvar inductive power is provided by SVC, the 2nd parallel resonance point is 1 Hz away from the previous resonance point. The input impedance value on the parallel resonance point between 135 and 178 Hz is significantly increased. However, if the TCR inductive power is limited to 60 Mvar, the change of impedance value on 177 Hz resonance point will not be large. Therefore, the harmonic content generated by the TCR branch can be controlled properly.

    Theoretically, the maximum 3-phase dc magnetic biasing current caused by the magnetic storm on a 750 kV system is 200 A. For each phase, the current is 66.7 A. The 4th harmonic parallel resonance betweenZsysandZSVCis most likely to occur when two FC branches are switched on for compensatingQdccaused by 53 to 68 A dc magnetic biasing current. This should be avoided.

    3.2 Effect of the proposed resonance control procedure

    As the operating voltage on the low-voltage side of the transformer is 1.05 times the normal voltage(Ur=1.05UN), the parameters of FC branches in each SVC device are reconfigured as shown in Tab.5. In this configuration, the by-pass switch is only installed on the 7th FC branch. During normal operation, the inductance stays at 10.03 mH. Under magnetic biasing conditions, the switch is cut-off and increases the inductance into 17.08 mH. The structure of the whole UHVT-PSVC after modification is shown in Fig.15.

    Tab.5 Parameters of the reconfigured FC branches in SVC

    Fig.15 Structure of UHVT-PSVC after modification

    During normal operation, the impedance on the low-voltage side of the transformer and all branches in SVC are shown in Figs.16 and 17 whenKis set to be 12%, 7% and 4%. It is confirmed that the SVC device after reconfiguration can reduce the 3rd,5th and 7th harmonics significantly. All branch impedances above the 3rd harmonic can remain inductive.

    Fig.16 Impedance/frequency characteristics on the low-voltage side of the transformer with 3 FC branches (no magnetic biasing)

    If no magnetic biasing is detected, and switchKin the 7th order FC branch is accidentally turned off, in this case, the 7th harmonic series-reactance rate will increase to 7%. The impedance characteristics on the low-voltage side of the transformer with different branches are shown in Fig.18.

    (a)

    (a)

    Comparing Fig.16 with Fig.18, it is fair to say that the SVC with a new configuration can properly set the system parallel resonance point away from the 2nd ,3rd and 4th harmonics during normal operation. No negative influence can be found in this process.

    If magnetic biasing is detected, the bypass switch is turned off, which increases theKvalue of FC branches to 12%,7% and 7%. The changes of input impedance characteristics on the low-voltage side of the transformer with the decrease inXt(i.e. increasing of magnetic biasing condition) are shown in Figs.19 and 20.

    (a)

    Apparently, by adjusting theKvalue of FC branches, two parallel resonance points of the input impedance on the low-voltage side can be controlled far away from the 3rd and 4th harmonics. Even with strong magnetic biasing (Xtdrops to only 57.29%), the 4th harmonic impedance of the system can still be kept inductive, preventing the corresponding parallel resonance. The impedance changes of SVC devices with different FC branches are shown in Fig.21.

    It is proved that the 4th harmonic impedance of the SVC can be kept inductive for all the switching patterns. Harmonic amplification can also be prevented.

    To conclude, the proposed resonance fault control device and its corresponding resonance control method can prevent the system from parallel resonance or harmonic amplification under different magnetic biasing without influencing the normal compensation of SVC. It can also reduce harmonic efficiently during normal operation. The fault control method is proved to be valid and can improve system stability.

    (a)

    (a)

    4 Conclusions

    1) Under magnetic biasing, if the series-reactance rates of 3 FC branches in SVC are lower than 12%,6% and 6%, the 4th harmonic resonance and harmonic amplification will occur on the low-voltage side of the transformer.Although the reactive power loss of the transformer may be compensated by SVC, the potential resonance fault should still be avoided due to the potential harmonic amplification.

    2) By using the proposed resonance control method, the series-reactance rates of all branches are adjusted to 12%, 7% and 4%/7% (without/with magnetic biasing). Combined with the restriction of TCR capacity, it can eliminate the 4th harmonic resonance and amplification under magnetic biasing.

    3) The magnetic-field coupling model of the transformer based on J-A hysteresis can simulate the dynamic parameter and reactive power loss under various conditions. With the assistance of the impedance/frequency analysis model of UHVT-PSVC, the connections between the magnetic biasing current and equivalent impedance can be analyzed properly under various conditions. This provides a valid solution for the simulation of the impedance/frequency characteristics for different equipment under different magnetic biasing.

    校园春色视频在线观看| 男女午夜视频在线观看| 女生性感内裤真人,穿戴方法视频| 免费人成视频x8x8入口观看| 欧美黄色淫秽网站| 女人爽到高潮嗷嗷叫在线视频| 热re99久久精品国产66热6| 亚洲国产看品久久| 国产成人精品久久二区二区91| 久久午夜亚洲精品久久| 国产人伦9x9x在线观看| 亚洲va日本ⅴa欧美va伊人久久| 亚洲 国产 在线| 宅男免费午夜| 国产精品久久视频播放| 级片在线观看| 欧美不卡视频在线免费观看 | 午夜老司机福利片| 久久久久久久久中文| 丰满饥渴人妻一区二区三| 亚洲国产看品久久| 色精品久久人妻99蜜桃| 法律面前人人平等表现在哪些方面| 高清欧美精品videossex| 自线自在国产av| 日韩三级视频一区二区三区| 别揉我奶头~嗯~啊~动态视频| 亚洲情色 制服丝袜| 97人妻天天添夜夜摸| 在线视频色国产色| 中文字幕另类日韩欧美亚洲嫩草| 成人国语在线视频| 国产精品乱码一区二三区的特点 | 久久久国产精品麻豆| 制服诱惑二区| 淫妇啪啪啪对白视频| 精品少妇一区二区三区视频日本电影| 国产91精品成人一区二区三区| 夜夜爽天天搞| 午夜成年电影在线免费观看| 侵犯人妻中文字幕一二三四区| 国产又爽黄色视频| 久久99一区二区三区| 十分钟在线观看高清视频www| 在线观看免费高清a一片| 热re99久久精品国产66热6| 久久精品国产清高在天天线| 欧美乱妇无乱码| 国产精品一区二区在线不卡| 黑人巨大精品欧美一区二区mp4| 国产不卡一卡二| 久久人妻熟女aⅴ| 欧美中文日本在线观看视频| 亚洲一区中文字幕在线| 久久精品国产亚洲av香蕉五月| 日本a在线网址| 女人被狂操c到高潮| 91在线观看av| 国产成人系列免费观看| 国产精品二区激情视频| 交换朋友夫妻互换小说| 精品欧美一区二区三区在线| 人人澡人人妻人| 亚洲熟女毛片儿| 精品国产美女av久久久久小说| 国产精品av久久久久免费| 久久久精品国产亚洲av高清涩受| 中文字幕高清在线视频| 在线观看一区二区三区激情| cao死你这个sao货| 日韩欧美在线二视频| 一边摸一边抽搐一进一出视频| 久久国产乱子伦精品免费另类| 国产精品自产拍在线观看55亚洲| 91麻豆av在线| 手机成人av网站| 亚洲国产看品久久| 久久精品亚洲av国产电影网| 窝窝影院91人妻| 欧美日韩亚洲高清精品| 91av网站免费观看| 成人三级做爰电影| 国产视频一区二区在线看| 欧美老熟妇乱子伦牲交| 别揉我奶头~嗯~啊~动态视频| 啦啦啦在线免费观看视频4| 亚洲国产欧美日韩在线播放| 亚洲人成77777在线视频| 国产欧美日韩综合在线一区二区| 国产在线精品亚洲第一网站| 丝袜在线中文字幕| 天天添夜夜摸| 亚洲第一欧美日韩一区二区三区| 色婷婷久久久亚洲欧美| 他把我摸到了高潮在线观看| 成人黄色视频免费在线看| 午夜免费鲁丝| 18禁观看日本| 精品国产乱码久久久久久男人| 可以免费在线观看a视频的电影网站| 又黄又粗又硬又大视频| 国产免费av片在线观看野外av| 日韩高清综合在线| 可以在线观看毛片的网站| 三上悠亚av全集在线观看| 国产黄a三级三级三级人| 一级作爱视频免费观看| 美国免费a级毛片| 亚洲国产毛片av蜜桃av| 中国美女看黄片| 国产精品一区二区在线不卡| 丝袜在线中文字幕| 黄频高清免费视频| 久久热在线av| 男人舔女人的私密视频| 一夜夜www| 亚洲精品国产一区二区精华液| 精品福利观看| 岛国视频午夜一区免费看| 青草久久国产| 精品国产国语对白av| 村上凉子中文字幕在线| 18美女黄网站色大片免费观看| 成人影院久久| 亚洲精品在线美女| 色综合站精品国产| 国产亚洲欧美精品永久| 悠悠久久av| 亚洲中文av在线| 两人在一起打扑克的视频| xxx96com| 18禁观看日本| 午夜亚洲福利在线播放| 国产aⅴ精品一区二区三区波| 亚洲一区二区三区色噜噜 | 黄色丝袜av网址大全| 国产亚洲精品久久久久久毛片| 欧美黑人欧美精品刺激| 亚洲成国产人片在线观看| 色婷婷久久久亚洲欧美| 亚洲第一青青草原| 亚洲人成伊人成综合网2020| 老司机深夜福利视频在线观看| 欧美黑人精品巨大| 别揉我奶头~嗯~啊~动态视频| 亚洲av成人一区二区三| 少妇被粗大的猛进出69影院| 欧美乱妇无乱码| 中文字幕高清在线视频| 国产蜜桃级精品一区二区三区| 大香蕉久久成人网| 一本大道久久a久久精品| avwww免费| 午夜免费激情av| 欧美最黄视频在线播放免费 | 午夜精品在线福利| 成人永久免费在线观看视频| 国产一卡二卡三卡精品| av片东京热男人的天堂| 日本黄色视频三级网站网址| 亚洲av日韩精品久久久久久密| 在线av久久热| 亚洲中文字幕日韩| 久久中文字幕人妻熟女| 91老司机精品| 韩国精品一区二区三区| 男女下面插进去视频免费观看| 黄色丝袜av网址大全| 国产高清视频在线播放一区| av超薄肉色丝袜交足视频| 9色porny在线观看| 日本五十路高清| 精品免费久久久久久久清纯| 国产成人av激情在线播放| 好男人电影高清在线观看| 狠狠狠狠99中文字幕| xxx96com| 欧美av亚洲av综合av国产av| 欧美乱妇无乱码| 91九色精品人成在线观看| 日韩精品免费视频一区二区三区| 日本一区二区免费在线视频| 精品少妇一区二区三区视频日本电影| 久久中文字幕人妻熟女| 搡老乐熟女国产| 亚洲专区中文字幕在线| 精品福利永久在线观看| 色综合婷婷激情| 妹子高潮喷水视频| 国产精品国产av在线观看| 51午夜福利影视在线观看| 一进一出抽搐动态| 热re99久久国产66热| 亚洲熟女毛片儿| 亚洲专区字幕在线| x7x7x7水蜜桃| 午夜激情av网站| 国产av在哪里看| 一个人观看的视频www高清免费观看 | 日韩欧美国产一区二区入口| 亚洲av第一区精品v没综合| 99精品久久久久人妻精品| 精品免费久久久久久久清纯| 精品人妻1区二区| 成人三级黄色视频| 日韩欧美免费精品| 久久久国产成人精品二区 | av视频免费观看在线观看| 国产有黄有色有爽视频| x7x7x7水蜜桃| 国产精品亚洲一级av第二区| 午夜亚洲福利在线播放| 91大片在线观看| 午夜免费成人在线视频| 国产精品成人在线| 欧美日韩瑟瑟在线播放| 欧美日韩中文字幕国产精品一区二区三区 | 日韩高清综合在线| 久久精品国产综合久久久| 亚洲精品久久成人aⅴ小说| 精品无人区乱码1区二区| 中文字幕av电影在线播放| 啦啦啦免费观看视频1| 欧美精品一区二区免费开放| 激情在线观看视频在线高清| 成人免费观看视频高清| 精品欧美一区二区三区在线| 日韩欧美国产一区二区入口| 久久人人精品亚洲av| 久久天躁狠狠躁夜夜2o2o| 久久 成人 亚洲| 亚洲第一av免费看| 99热国产这里只有精品6| 女性被躁到高潮视频| a级片在线免费高清观看视频| 一边摸一边抽搐一进一小说| 正在播放国产对白刺激| 亚洲人成网站在线播放欧美日韩| 国产亚洲精品第一综合不卡| 岛国在线观看网站| 日本 av在线| 男人的好看免费观看在线视频 | 91精品三级在线观看| 欧美成狂野欧美在线观看| 50天的宝宝边吃奶边哭怎么回事| 夜夜看夜夜爽夜夜摸 | 国产亚洲精品第一综合不卡| 国产精品爽爽va在线观看网站 | 久久久久久人人人人人| 久久精品人人爽人人爽视色| 99久久国产精品久久久| 夜夜躁狠狠躁天天躁| 国产成+人综合+亚洲专区| 午夜免费成人在线视频| 国产精品爽爽va在线观看网站 | 欧美日韩国产mv在线观看视频| 国产99白浆流出| 国产蜜桃级精品一区二区三区| 免费女性裸体啪啪无遮挡网站| 欧美人与性动交α欧美精品济南到| e午夜精品久久久久久久| 黄片播放在线免费| 一边摸一边做爽爽视频免费| 亚洲国产精品sss在线观看 | 高清av免费在线| 成人av一区二区三区在线看| 日韩大码丰满熟妇| 手机成人av网站| 琪琪午夜伦伦电影理论片6080| 欧美日韩亚洲国产一区二区在线观看| 国产av在哪里看| 欧美日韩视频精品一区| 国产亚洲精品久久久久久毛片| 精品免费久久久久久久清纯| 91九色精品人成在线观看| 亚洲熟妇中文字幕五十中出 | 啦啦啦 在线观看视频| 日韩欧美在线二视频| 婷婷精品国产亚洲av在线| 免费看十八禁软件| 美女国产高潮福利片在线看| 少妇裸体淫交视频免费看高清 | 欧美黄色片欧美黄色片| 午夜成年电影在线免费观看| 日韩 欧美 亚洲 中文字幕| bbb黄色大片| 热re99久久精品国产66热6| 免费人成视频x8x8入口观看| www日本在线高清视频| 国产亚洲欧美在线一区二区| 夜夜躁狠狠躁天天躁| 久久精品aⅴ一区二区三区四区| 日本wwww免费看| 天堂俺去俺来也www色官网| 狠狠狠狠99中文字幕| 国产激情欧美一区二区| 久久中文看片网| 免费久久久久久久精品成人欧美视频| 啦啦啦免费观看视频1| aaaaa片日本免费| 国产一区二区三区视频了| 免费人成视频x8x8入口观看| 色老头精品视频在线观看| 国产一区二区三区在线臀色熟女 | av在线天堂中文字幕 | 国产一卡二卡三卡精品| 男女高潮啪啪啪动态图| 国产又色又爽无遮挡免费看| 色综合欧美亚洲国产小说| 最好的美女福利视频网| 亚洲一区二区三区欧美精品| 亚洲精品久久午夜乱码| 两个人免费观看高清视频| tocl精华| 欧美人与性动交α欧美软件| 久久久久久久午夜电影 | 黑丝袜美女国产一区| 久久人人爽av亚洲精品天堂| 少妇被粗大的猛进出69影院| 午夜久久久在线观看| 免费看a级黄色片| 99精品久久久久人妻精品| 一边摸一边做爽爽视频免费| 日韩大码丰满熟妇| 欧美成人午夜精品| 1024视频免费在线观看| av免费在线观看网站| 中文字幕人妻丝袜制服| 欧美日韩国产mv在线观看视频| 亚洲精品美女久久av网站| 90打野战视频偷拍视频| 黄片播放在线免费| 99精品欧美一区二区三区四区| 国产精品永久免费网站| 日韩欧美一区视频在线观看| 精品久久久久久成人av| 男女下面进入的视频免费午夜 | 亚洲欧美一区二区三区黑人| 国产伦一二天堂av在线观看| 极品教师在线免费播放| 黑人操中国人逼视频| 黄色视频不卡| 窝窝影院91人妻| 亚洲熟妇中文字幕五十中出 | 国产精品自产拍在线观看55亚洲| 在线观看舔阴道视频| 午夜福利免费观看在线| 男男h啪啪无遮挡| 黄色视频不卡| 一级毛片高清免费大全| 久久久国产精品麻豆| 国产成人免费无遮挡视频| 国产成年人精品一区二区 | 亚洲狠狠婷婷综合久久图片| 亚洲欧美一区二区三区久久| 香蕉丝袜av| 女人爽到高潮嗷嗷叫在线视频| 久久久久久久午夜电影 | 欧美成人性av电影在线观看| 超碰成人久久| 久久99一区二区三区| 色婷婷久久久亚洲欧美| 一个人观看的视频www高清免费观看 | 91老司机精品| 一二三四社区在线视频社区8| 制服人妻中文乱码| 日韩欧美三级三区| 亚洲精品久久午夜乱码| 久久香蕉国产精品| 亚洲午夜理论影院| 极品教师在线免费播放| 欧美人与性动交α欧美软件| 国产成人精品无人区| 免费在线观看视频国产中文字幕亚洲| 国产亚洲精品久久久久5区| 精品国产国语对白av| 成在线人永久免费视频| 日韩国内少妇激情av| 欧美激情高清一区二区三区| 欧美人与性动交α欧美软件| 国产成人精品无人区| 曰老女人黄片| 亚洲精华国产精华精| 欧美日韩av久久| av超薄肉色丝袜交足视频| 黄色成人免费大全| 99riav亚洲国产免费| 亚洲五月色婷婷综合| 久久精品91无色码中文字幕| 一边摸一边做爽爽视频免费| 国产av又大| 99久久久亚洲精品蜜臀av| 国产av又大| 亚洲成人久久性| 99在线视频只有这里精品首页| 亚洲一区二区三区色噜噜 | 国产精品一区二区精品视频观看| 免费看十八禁软件| 亚洲一区二区三区色噜噜 | 午夜两性在线视频| 波多野结衣一区麻豆| 老汉色∧v一级毛片| tocl精华| 日韩精品青青久久久久久| 美女 人体艺术 gogo| 午夜免费成人在线视频| 亚洲欧美精品综合久久99| 一级a爱片免费观看的视频| 一级片'在线观看视频| 久久亚洲精品不卡| 国产人伦9x9x在线观看| 老汉色av国产亚洲站长工具| 日日摸夜夜添夜夜添小说| 国产一区二区激情短视频| 午夜日韩欧美国产| 日韩欧美免费精品| 国产乱人伦免费视频| av超薄肉色丝袜交足视频| 一边摸一边做爽爽视频免费| 69精品国产乱码久久久| 国产av在哪里看| 狂野欧美激情性xxxx| 巨乳人妻的诱惑在线观看| 成人三级做爰电影| 宅男免费午夜| xxxhd国产人妻xxx| 亚洲性夜色夜夜综合| 搡老熟女国产l中国老女人| 香蕉丝袜av| 一边摸一边抽搐一进一出视频| 亚洲精华国产精华精| 一区二区三区激情视频| 视频区图区小说| 国产三级在线视频| 亚洲成国产人片在线观看| 国产精品香港三级国产av潘金莲| 国产片内射在线| 中文字幕人妻丝袜一区二区| 黑丝袜美女国产一区| 怎么达到女性高潮| 亚洲人成77777在线视频| 女人爽到高潮嗷嗷叫在线视频| 午夜亚洲福利在线播放| 在线观看66精品国产| 香蕉国产在线看| 三上悠亚av全集在线观看| 免费不卡黄色视频| 巨乳人妻的诱惑在线观看| svipshipincom国产片| 91麻豆精品激情在线观看国产 | 久久久久久大精品| 国产精品久久久久成人av| cao死你这个sao货| 动漫黄色视频在线观看| 久久久国产成人免费| 精品人妻1区二区| 中出人妻视频一区二区| 午夜免费观看网址| 美女福利国产在线| 51午夜福利影视在线观看| 变态另类成人亚洲欧美熟女 | 精品第一国产精品| 国产精品日韩av在线免费观看 | 国产真人三级小视频在线观看| 国产av一区在线观看免费| 亚洲av美国av| 丁香六月欧美| 极品教师在线免费播放| 97人妻天天添夜夜摸| 欧美成狂野欧美在线观看| 老熟妇仑乱视频hdxx| 国产成人av教育| 日本欧美视频一区| 一级片'在线观看视频| 美女大奶头视频| 亚洲欧美精品综合久久99| 国产一卡二卡三卡精品| 亚洲中文日韩欧美视频| а√天堂www在线а√下载| 国产精品1区2区在线观看.| 国产精品偷伦视频观看了| www.自偷自拍.com| 亚洲男人的天堂狠狠| 91精品三级在线观看| 搡老熟女国产l中国老女人| 母亲3免费完整高清在线观看| 一区二区三区激情视频| 日本vs欧美在线观看视频| 亚洲片人在线观看| 高潮久久久久久久久久久不卡| 90打野战视频偷拍视频| 老熟妇乱子伦视频在线观看| 欧美人与性动交α欧美精品济南到| 免费看a级黄色片| 色尼玛亚洲综合影院| 国产一区二区三区视频了| 老司机午夜十八禁免费视频| 国产精品香港三级国产av潘金莲| 精品一区二区三区av网在线观看| 亚洲av电影在线进入| 97人妻天天添夜夜摸| 99精品久久久久人妻精品| 国产精品久久久av美女十八| 国产精品一区二区免费欧美| 国产精品自产拍在线观看55亚洲| 亚洲五月色婷婷综合| 美女 人体艺术 gogo| 在线观看免费视频网站a站| 久久青草综合色| 久久中文字幕一级| 天堂俺去俺来也www色官网| aaaaa片日本免费| 少妇被粗大的猛进出69影院| 午夜免费鲁丝| 亚洲av电影在线进入| 国产精品98久久久久久宅男小说| 亚洲人成电影免费在线| 日韩精品免费视频一区二区三区| 一级毛片女人18水好多| 在线看a的网站| 超碰97精品在线观看| 性欧美人与动物交配| 午夜免费观看网址| 精品久久久精品久久久| 国产精品偷伦视频观看了| 亚洲全国av大片| 国产成人啪精品午夜网站| 亚洲精品国产精品久久久不卡| 一本大道久久a久久精品| 亚洲黑人精品在线| 欧美日韩亚洲高清精品| www国产在线视频色| 一进一出好大好爽视频| 韩国av一区二区三区四区| 日韩人妻精品一区2区三区| 亚洲熟女毛片儿| 国产精品秋霞免费鲁丝片| 国产蜜桃级精品一区二区三区| 男男h啪啪无遮挡| 一级,二级,三级黄色视频| 女人被躁到高潮嗷嗷叫费观| 精品久久久久久成人av| 色综合站精品国产| 久久国产精品影院| 精品无人区乱码1区二区| 国产欧美日韩一区二区三| 久久精品国产综合久久久| 十八禁人妻一区二区| 国产精品影院久久| 最新美女视频免费是黄的| 精品国产乱码久久久久久男人| 精品高清国产在线一区| 久久久久国内视频| 日韩欧美国产一区二区入口| 天堂影院成人在线观看| av有码第一页| 亚洲五月色婷婷综合| 老司机午夜十八禁免费视频| 丁香欧美五月| 亚洲男人的天堂狠狠| 久久精品人人爽人人爽视色| 黑人巨大精品欧美一区二区mp4| 精品久久久久久电影网| 亚洲,欧美精品.| 香蕉久久夜色| 波多野结衣一区麻豆| 国产精品香港三级国产av潘金莲| 中文字幕高清在线视频| 久久精品国产亚洲av高清一级| 999精品在线视频| 成熟少妇高潮喷水视频| 亚洲av日韩精品久久久久久密| av免费在线观看网站| 操美女的视频在线观看| 国产精品一区二区三区四区久久 | 精品日产1卡2卡| 成年人免费黄色播放视频| 97人妻天天添夜夜摸| 国产麻豆69| 亚洲激情在线av| 免费在线观看视频国产中文字幕亚洲| 亚洲一卡2卡3卡4卡5卡精品中文| 久久狼人影院| 亚洲精品久久午夜乱码| 国产精品 国内视频| 午夜免费成人在线视频| 黄色a级毛片大全视频| 免费人成视频x8x8入口观看| 亚洲精品在线观看二区| 久久国产精品人妻蜜桃| 亚洲精品中文字幕一二三四区| 18禁观看日本| 在线播放国产精品三级| 国产亚洲精品久久久久5区| 欧美亚洲日本最大视频资源| 一级片'在线观看视频| 亚洲av日韩精品久久久久久密| 亚洲欧美激情在线| 色综合欧美亚洲国产小说| 亚洲中文av在线| 少妇 在线观看| av片东京热男人的天堂| 亚洲精品美女久久av网站| 欧美日韩av久久| 久久精品亚洲av国产电影网| 在线观看一区二区三区| 丁香六月欧美| 超色免费av| 国产精品香港三级国产av潘金莲| 亚洲午夜理论影院| 波多野结衣一区麻豆| 另类亚洲欧美激情| 久久精品亚洲熟妇少妇任你| 国产成人一区二区三区免费视频网站| 欧美黄色片欧美黄色片|