    Self-Powered Active Vibration Control: Concept, Modeling, and Testing

    2022-06-11 09:03:28JinYngLiSongyeZhu
    Engineering 2022年4期

    Jin-Yng Li, Songye Zhu,b,*

    a Department ofCivil and Environmental Engineering,TheHong KongPolytechnic University,Hong Kong999077,China

    b NationalRailTransitElectrification and Automation EngineeringTechnology ResearchCenter(HongKongBranch),TheHong Kong Polytechnic University, Hong Kong 999077,China

    Keywords:Self-powered active vibration control Energy harvesting Skyhook control Power equilibrium Smart control

    ABSTRACT Despite their superior control performance,active vibration control techniques cannot be widely used in some engineering fields because of their substantial power demand in controlling large-scale structures.As an innovative solution to this problem,an unprecedented self-powered active vibration control system was developped in this study. The topological design, working mechanism, and power flow of the proposed system are presented herein. The self-powering ability of the system was confirmed based on a detailed power flow analysis of vibration control processes. A self-powered actively controlled actuator was designed and applied to a scaled active vibration isolation table. The feasibility and effectiveness of the innovative system were successfully validated through a series of analytical,numerical,and experimental investigations.The setup and control strategy of the proposed system can be readily extended to diversified active vibration control applications in various engineering fields.

    1. Introduction

    Vibration control(also known as vibration suppression or isolation) refers to a family of techniques for the protection of primary structures or systems against excessive vibrations induced by dynamic loads. Vibration control is widely utilized in aerospace,mechanical, and civil structures for noise control [1], vehicle suspension-related applications [2,3], satellite vibration suppression [4], and protection of large-scale civil infrastructures against extreme earthquakes and typhoons [5]. Existing vibration control techniques are generally categorized as passive, semi-active, or active techniques [6], each of which possesses unique advantages and disadvantages. Passive control devices, which do not require any feedback systems and power input, suppress undesired vibrations by modifying the inherent structural properties and/or dissipating structural kinetic energy. In contrast, active control offers the best control performance by exerting optimized active control forces based on feedback signals.However,its high power demand hinders its application in controlling large-scale structures (e.g.,civil infrastructure), particularly considering the limited power availability in remote locations. Semi-active control lies between passive and active controls;it can typically achieve a more efficient control performance than its passive counterpart but consumes less input power than its active counterpart. Table 1 summarizes the conventional views on the three types of vibration control techniques.

    However,these conventional views are being increasingly challenged by the latest technological developments in the field of structural vibration control. For example, the power demands of passive and semi-active controls have recently been redefined via emerging vibration-based energy harvesting technology.The introduction of dual-functional dampers with simultaneous vibration damping and energy harvesting functions presents the exciting advancement of passive dampers from energy dissipating to energy regenerating mode (i.e., from zero to negative power consumption),wherein electromagnetic(EM)dampers enable the conversion of kinetic energy to electric energy,and the latter is further stored in capacitors or rechargeable batteries for later use [7,8].Given the adoption of EM dampers in existing vibration control devices (such as EM mass dampers or driver systems [9,10], EM shunt dampers [11], and EM inerter dampers [12,13]), such an energy harvesting paradigm can be conveniently introduced in a variety of vibration control applications. For example, energy regenerative tuned mass dampers (TMDs) have been developed for high-rise buildings by combining classical TMDs and energy harvesting passive dampers [7,14]. Zhang et al. [15] reviewed the recent developments and investigations on energy regenerative shock absorbers. The energy regenerative braking system forelectric vehicles represents another important application field of such energy harvesting passive damping devices [16–19].

    Table 1 Comparison of different types of vibration control techniques.

    Researchers have also started to explore self-powered semiactive vibration control technologies. For example, Cho et al. [20]proposed a combination of a magnetorheological (MR) damper and an EM induction device, wherein the latter served as a power source for the former. This self-powered semi-active control system was later tested in a laboratory experiment on a full-scale cable [21]. Chen and Liao [22] further upgraded the mentioned prototype by integrating the EM and MR components and verified the system experimentally.

    Developing self-powered active vibration control presents a more revolutionary and challenging task. The existing attempts were mainly focused on two strategies. The first involves using two separate units to perform energy-harvesting and active control functions, similar to that of the aforementioned semi-active solution.Scruggs and Iwan[23]proposed an energy-regenerative actuation network that extracts vibration energy from one location and applies it to another location. Suda et al. [24] explored a selfpowered active vehicle suspension with an energy-harvesting motor installed in the primary suspension and another active EM actuator installed in the secondary suspension.The second strategy involves operating control devices alternately in passive (energyharvesting) and active (energy-consuming) modes. Nakano and Suda [25] subsequently applied the same system design (Ref.[24]) to a suspension for a truck cabin. Tang and Zuo [26] utilized an active TMD to develop clipped linear–quadratic–Gaussian(LQG)control algorithms.However,in these two strategies,active control still needs to rely on an additional power source; otherwise, the active control force cannot be fully produced. Therefore, neither of these two strategies can be regarded as a truly self-powered active vibration control strategy.

    Fig. 1. Typical control force–velocity relationship in an active vibration isolation system. Q: quadrant.

    The feasibility of a truly self-powered active vibration control system remains to be proven. Accordingly, we should first revisit the power flow in an active vibration control system. Fig. 1 shows a representative force–velocity relationship produced using an actively controlled actuator in a vibration isolation system. If the curve is in the first and third quadrants, the transient power of the active actuator is positive (i.e., power-harvesting), whereas if the curve is in the second and fourth quadrants, the transient power is negative (i.e., power-consuming). Therefore, if the enclosed area in the first and third quadrants is greater than that in the other two quadrants, the net output power will be positive(Fig. 1). Can we extend this conclusion to a generic vibration control case? Notably, active vibration control refers to a special subset of structural control technology with the unique goal of minimizing the vibration energy of a host structure. To prevent any control instability problem, an overall energy injection into the host structure (i.e., negative net output energy) should be avoided, although a negative transient power flow is allowable.Thus, theoretically, the active control can be self-powered if the transient output power can be efficiently stored and utilized subsequently in the vibration cycles.

    The realization of such a concept, which will certainly involve more challenges and will be more complex than the above ideal situation, has never been explored. This paper presents the first attempt to develop a novel self-powered active vibration control system. The topology, working mechanism, and a power analysis of the system are first introduced and discussed herein. The proposed system was then implemented on an active vibration isolation table using the classical skyhook control algorithm.Subsequently, the active control performance and self-powered feasibility were successfully validated through numerical and experimental investigations.

    2. Self-powered active actuator design

    2.1. System topology

    Fig.2 shows a single-degree-of-freedom(SDOF)vibration isolation system with the proposed self-powered actively controlled actuator under seismic excitation. The self-powered active control system comprises four modules: an EM actuator, an H-bridgebased power electronics circuit with a rechargeable battery, a microcontroller unit (MCU), and a sensory system.

    The EM actuator can produce a control force compatible with large-scale structures[27,28].In the circuit model,the EM actuator is represented by a back electromotive force (EMF, Vm) and by the inner resistor(R0)and inductor(L0)of the coil.The relative motion of the EM actuator generates EMF, while the current (i) passing through the EM actuator generates the control force (Fctrl).

    where Kemis the motor constant, which is solely dependent on the properties of the EM actuator; .x and .xgare the absolute velocities of the structure and ground, respectively; and .x- .xgrepresents the relative velocity experienced by the EM actuator. The negative sign of Fctrlindicates that a positive current will result in a downward force on the isolated mass (mh).

    The MCU determines the target control force based on the received sensing signals and translates it into pulse-width modulation (PWM) signals to manipulate the H-bridge circuit. In this study,an open-source MCU platform(Arduino Uno)was employed to fulfill the integrated functions of data sensing and acquisition,data processing, control algorithm execution, and data output.The analog sensing signals (including the absolute and relative velocities in this study) were collected and digitalized through an onboard analog to digital (A/D) converter. Then, the control algorithm code was uploaded to Arduino through a C language-based embedded integrated development environment (IDE), which determined the duty cycle of the PWM signals.

    Fig.2. Schematic of the proposed self-powered active control system.mh:isolated mass of the host structure;kh:stiffness of the host structure;ch:damping coefficient of the host structure; Acc: acceleration; Vel: velocity; Fctrl: control force; A and B: two nodes of the EM device; M1–M4: four metal-oxide-semiconductor field-effect transistors(MOSFETs);Arduino:the open-source MCU platform(https://www.arduino.cc/);R0:the inner resistor;L0:the inner inductor;Sig 1 and Sig 2:pulse-width modulation(PWM)signals.

    The H-bridge circuit allows bidirectional power flow, thereby serving as a typical switch-mode rectifier[29].Although traditionally used in motor driver circuits,the H-bridge circuit has recently attracted interest in the energy-harvesting field[30].Liu et al.[31]employed an H-bridge circuit controlled using PWM waves to enhance the energy-harvesting efficiency of piezoelectric materials. A similar H-bridge interface was used to tune EM energy harvesters to improve the energy harvesting efficiency [32,33]. Hsieh et al. [29] adopted an H-bridge topology in an energyregenerative suspension system by emulating various resistances and realizing semi-active skyhook control.

    In this study, the H-bridge circuit served as an actuator driver and an energy-harvesting circuit. As shown in Fig. 2, the Hbridge power circuit is the interface between the EM actuator and the rechargeable battery,controlling the charge and discharge of the battery. The H-bridge circuit comprises four metal–oxide–semiconductor field-effect transistors (MOSFETs). Two diagonal MOSFET sets, namely M1–M4and M2–M3, were controlled via PWM signals Sig 1 and Sig 2, respectively, and each diagonal set was switched on and off simultaneously at a high alternating frequency (starting from thousands of hertz). Four N-type MOSFETs(i.e.,N-MOS)were adopted in this study and were‘‘on”only when the PWM signals on their gate nodes were at high levels (i.e., over threshold voltage (VGS)). Considering the voltage fluctuation at nodes A and B in Fig.2,high-side MOSFETs(i.e.,M1and M3)require an extra bootstrap circuit or a gate driver for control.

    Meanwhile, the rechargeable battery served as both a powerstorage and power-supply element. Apart from rechargeable batteries, supercapacitors are frequently used in energy-harvesting applications. However, since a rechargeable battery can maintain a more stable voltage (Vbatt) than a supercapacitor, nickel–metal hydride (Ni-MH) batteries were adopted in the proof-of-concept tests in this study.diagonal sets are alternated between‘‘on”and‘‘off.”Consequently,the duty cycles (D1and D2) of Sig 1 and Sig 2 should satisfy the approximate relationship D1+ D2= 1. If the switching period of the PWM signals is TPWM= 1/fPWM, where fPWMis the PWM frequency, then M1and M4are on (Sig 1 is high), and M2and M3are off(Sig 2 is low)during t1=TPWM?D1.Consequently,node A connects to the positive pin of the power source,and node B connects to the ground.When the control signal flips in a PWM cycle,Sig 1 is low and Sig 2 is high for the remaining duration of t2= TPWM?(1 –D1).

    If the current(i)in the actuator and the inductor is assumed to be positive when flowing from right to left, then each switching cycle has the following relationships according to Kirchhoff’s voltage law:

    where Vmis the instantaneous EMF, Vbattis the voltage of the rechargeable battery,and Rtotalis the total circuit resistance,including the motor inner resistance (R0) and the resistances of the battery, connecting wires, and other electrical elements (e.g.,MOSFETs). In each PWM cycle with an extremely short duration,Vmand Vbattcan be regarded as nearly constant, current i is in a steady state, and the total change in the current should be nearly zero. Consequently, the current flowing through the EM actuator can be estimated by solving Eqs. (2) and (3), as follows:

    2.2. System principle

    To avoid short-circuit-induced damage to the system,Sig 1 and Sig 2 can not be at high levels simultaneously, and thus the two

    Eq. (6) reveals that the achievable current range can be increased using a larger power source voltage (Vbatt).

    A laboratory experiment was conducted to verify the relationship in Eq.(4).In this experiment,the EM actuator was represented by the combination of an inductor (L0= 0.1 H), a resistor (Rtotal=16 Ω), and a battery (Vm= 2.5 V) that emulates a constant EMF.The voltage of the rechargeable battery (Vbatt) is 12 V. Four NMOSs (part No.: IRF840A) were used in the H-bridge, and the drain–source on-resistance of each was only RMOS= 0.85 Ω, which is considered in the total resistance(Rtotal)of the entire circuit.The experimental setup was nearly the same as that used in the SDOF test described in Section 3.2,except for the replacement of the EM actuator with a battery (i.e., a constant EMF). More detailed descriptions and images of the setup are provided in Section 3.2.Fig. 3 displays the relationship between the actuator current and duty cycle D1, whose theoretical result is based on Eq. (4). The simulation result was generated using the MATLAB Simulink toolbox.The consistency observed in Fig.3 confirms the accuracy of Eq.(4) and the Simulink model.

    Fig. 4 shows a schematic of the relationship between the control force (–Fctrl) and the relative velocity (.x- .xg) experienced by the EM actuator. As predicted using Eq. (5), the upper and lower bounds, corresponding to D1= 0 and 1, respectively,define the achievable range of the control force. Any desirable active control force within this range can be generated by regulating D1accordingly. The achievable range of the control force can be increased by adopting a larger power source voltage(Vbatt), a larger motor constant (Kem), and a reduced circuit resistance (Rtotal).

    2.3. Power analysis

    In this section,the power flow between the EM actuator and the rechargeable battery is discussed. Within a short PWM cycle, the current (i) flowing in the EM actuator, which is defined in Eq. (4),remains nearly constant; the current in the battery has the same amplitude but flows in both directions owing to the switching of the H-bridge circuit.Consequently,if the current(i)in the EM actuator is positive (from right to left), the battery is charged and discharged during t1and t2, respectively. Power harvesting or consumption depends on the relative durations of t1and t2. Thus,the average output power(P)within one PWM cycle,which is termed the instantaneous output power hereinafter,can be calculated as follows:

    The green shaded area in Fig. 3 shows the derived powerharvesting range when μ > 0 (i.e., Vm> 0).

    Substituting Eqs.(1)and(4)into Eq.(10)leads to the following power-harvesting condition in the force–velocity relation:

    However,the force–velocity relationship does not always fall in the green zone. To realize a self-powered active vibration control system, the average output power should remain positive over a given period.

    Fig. 3. Relationship between the current of the actuator and the duty cycle (D1) of the control signal.μ = Vm/Vbatt.

    Fig. 4. Partition of power-consuming and power-harvesting zones in the plane of active control force versus relative velocity of the actuator.

    The dashed loop in Fig. 4 indicates a representative control force–velocity relation in a vibration cycle. As long as the force–velocity loop covers more of the green area than of the yellow area,the active actuator can operate in an overall energy-harvesting mode. The rechargeable battery stores the harvested power temporarily in the green zone and reuses this power in the yellow zone to generate active control forces.

    Notably, the foregoing derivation is based on the assumption that the structural vibration frequency is considerably lower than the switch frequency of the H-bridge; the former typically ranges from less than one hertz to hundreds of hertz, whereas the latter typically exceeds thousands of hertz. Otherwise, the control force would not be successfully achieved through the proposed setup.

    3. Active vibration isolation with self-powered actuator

    The SDOF vibration isolation system with the proposed selfpowered active actuator (Fig. 2) was investigated numerically and experimentally to verify the vibration control and power performance. The skyhook control algorithm was employed to determine the active control force.

    3.1. Numerical modeling and control algorithm

    The equation of motion for the SDOF structure shown in Fig. 2 can be expressed as

    The classical skyhook control, which represents an ideal vibration isolation with a hypothetical viscous damper connecting the sprung mass to an immobile ceiling [34], was adopted to determine the active control force:

    The generated duty cycle(D1)is then passed to the H-bridge circuit to deliver the control force required by the skyhook control.Although only skyhook control was adopted in this study,the presented methodology can be easily applied to any other active control algorithm.

    Fig.5 shows a block diagram of the entire active control system,including the state-space model of the host structure, the ideal skyhook control, the feedforward control algorithm to determine the duty cycle, the H-bridge circuit, and the EM actuator. In addition to the EM force, the parasitic force of the EM actuator is considered in this diagram. The total control force of the EM actuator exerted on the host structure formed a closed loop.

    When the SDOF structure is subjected to harmonic ground excitation,¨xg=GAcos (ωt )where GAstands for amplitude of the ground motion,the instantaneous output power can be calculated by substituting Eqs. (1), (4), (15), and (16) into Eq. (8):

    where T = 2π/ω is the period of the harmonic excitation.

    Fig. 6 shows the entire self-powered active vibration isolation system modeled in MATLAB Simulink. The major parameters of the mechanical and electrical components were modeled in accordance with those used in the experiment.The simulated PWM frequency was 2 kHz, and the computation timestep of the Simulink model was set to 10-6s to ensure sufficient points within each duty cycle. Numerical simulations were performed to verify the theoretical results and guide the laboratory experimental design.

    Fig.5. Block diagram showing the self-powered active vibration isolation system with skyhook control algorithm.A,B,C,D,z,u,and y represent state matrix,input matrix,output matrix, feedforward matrix, state vector, input vector, and output vector, respectively; cp is parasitic damping coefficient.

    Fig. 6. Simulink model of the self-powered active vibration isolation system. Fcn: MATLAB function module; tgt: target; DC: duty cycle; PID: proportional–integral–derivative; s: saturation.

    3.2. Experimental setup

    Fig. 7 presents an overview of the experimental setup for the active vibration isolation plate (i.e., the SDOF system). The three main components (i.e., control module, H-bridge module, and SDOF system) are highlighted with gray rectangles.

    The vibration isolation plate consisted of a mass plate (#4 in Fig. 8) suspended by four vertical springs (#2), representing an SDOF structure oscillating in the vertical direction.The input signal from the signal generator was first amplified using a power amplifier and then used to drive a 355 mm × 355 mm shake table to excite the SDOF structure with the designed ground motions. An EM motor was installed between the mass plate and the shake table, functioning as a control actuator (EM motor B in Fig. 8).

    The absolute acceleration of the mass plate was measured using two accelerometers installed on the plate. The absolute velocity was subsequently obtained through real-time integration of the acceleration signals using an anti-aliasing signal convertor.The relative velocity between the isolated mass plate and shake table was measured using another EM motor, denoted as the sensing motor(i.e.,EM motor A in Fig.8).Given that the top plate was rigidly connected to the shake table,the two EM motors were installed in parallel with each other and experienced the same relative velocity.In addition,the current flowing in the EM control motor was recorded by measuring the voltage difference across a small-value sensing resistor (Rs= 1 Ω).

    The adopted MCU was an Arduino Uno board (Italy) with an ATmega328 (USA) microcontroller (clock speed of 16 MHz),14 digital input/output (I/O) pins, and four analog input pins. Its typical power consumption was approximately 250 mW. The power consumption can be significantly reduced by using other low-power MCUs, such as an Arduino Pro mini (Italy) or even a tailor-made MCU with all unnecessary parts and functions removed. The aforementioned absolute velocity of the mass plate,the open-circuit voltage of the EM sensing motor, and the current in the circuit were sensed by the MCU at a sampling frequency of 200 Hz.The MCU processed the sensing data and executed the control algorithm shown in the‘‘MCU”block in Figs.5 and 6.The control algorithm was coded in an open-source C language-based IDE provided by Arduino AG.The MCU outputs the PWM signal with a determined duty cycle (D1) at the switching frequency of 2 kHz,corresponding to the PWM cycle of 500 μs.

    The two nodes of the EM control motor,denoted as Nodes A and B in Figs. 2, 7, and 8, were connected to the H-bridge circuit and hence to the rechargeable battery set.Fig.9 shows the printed circuit board(PCB)layout and a photograph of the manufactured PCB(35 mm×60 mm)hosting the H-bridge circuit.The H-bridge comprised four N-MOSs, which were controlled through a full-bridge driver as shown in Fig. 7. This full-bridge driver was adopted mainly to trigger high-side MOSFETs that experienced fluctuating voltages at their source pins. The full-bridge driver received PWM signals from the MCU. The value of R1in Fig. 7 controls the deadtime between two inverted PWM signals and thus prevents short circuits. According to the user manual, R1= 10 kΩ, which was selected in this study, corresponds to a deadtime of 0.5 μs.The battery set comprised three Ni-MH batteries connected in series,providing a nominal voltage of 12 V.An additional inductor was incorporated into the circuit to increase the motor inductance(L0) and smoothen the current curve.

    Fig. 7. Overview of experimental setup. The meanings of the 16 pins of HIP4082 chip can be found in the corresponding data sheet https://www.renesas.com/www/doc/datasheet/hip4082.pdf(AHB and BHB:the high-side bootstrap supply of A and B nodes;AHS and BHS:the high-side source connection of A and B nodes;AHI,BHI,ALI,BLI,AHO,BHO,ALO,and BLO:the high-side and low-side,input and output of A and B nodes,respectively;VSS and VDD:negative and positive supply to control logic and lower gate drivers, respectively; DEL: turn-on delay; DIS: disable input; GND: ground; VCC: voltage common collector; R1: a 10 kΩ resistor).

    Fig. 8. (a) Photo and (b) schematic drawing of the experimental setup of the vibration isolation table. 1: top plate; 2: spring; 3: load cell; 4: mass plate; 5: EM motor A(sensing); 6: fixture; 7: accelerometers; 8: EM motor B (actuation); 9: base plate.

    Fig. 9. H-bridge module. (a) PCB layout and (b) image of the PCB prototype. PolyU CEE: Department of Civil and Environmental Engineering, The Hong Kong Polytechnic University.

    In addition to the sensing signals utilized in the feedback control, more sensors were installed to evaluate the vibration control and power performance.An additional accelerometer was installed to measure the input acceleration of the shake table.Two laser displacement transducers were used to measure the absolute displacement of the mass plate and the shake table. A load cell was used to measure the control force of the EM actuator. The sensing data were collected using a data acquisition system at a sampling frequency of 10 kHz.Meanwhile,the charge and discharge currents of the battery were measured using a separate data acquisition system at a sampling frequency of up to 100 kHz, which is 50 times the PWM switching frequency; this enabled determination of the duty cycle of the PWM signals.

    The major parameters of the experimental setup are summarized in Table 2,while the model numbers of the major equipment and items are presented in Table 3. The vibration isolation table was tested under harmonic ground accelerations with a constant acceleration amplitude of 0.18g and varying excitation frequencies of 3–15 Hz. Two damping coefficients, csky= 20 and 40 N?s?m-1,were implemented individually in the skyhook controller. The vibration control and power performance were evaluated in these test scenarios.

    3.3. Influence of time delay

    Fig. 10 displays a comparison between the experimental and target EM control forces. The former was calculated using Eq. (1)and the measured motor current, while the latter is the product of the measured absolute velocity of the mass plate and the coefficient csky= 40 N?s?m-1. Although the experimental control force matches the amplitude of the target control force very closely, an approximate time delay of τ = 0.01 s can be observed in this comparison.This delay is likely due to data processing,which involves sampling,A/D conversion,transmission,synchronization,and control algorithm execution. A typical method to mitigate the influence of the time delay is to use a compensator (such as a proportional–integral–derivative (PID) controller). However, no compensator was implemented in the control algorithm, as the influence of the time delay was insignificant in this study.

    Considering the time lag in the active control force,the theoretical transmissibility function in Eq. (16) can be rewritten as

    Table 2 Major parameters of the tested active vibration isolation system.

    Table 3 Model numbers of the equipment and items used in the experiment.

    The impact of the time delay is frequency-dependent and thus becomes more significant under high-frequency excitation. The time delay was also considered in the Simulink model by adding a delay module before the control force was applied to the host structure, as shown in Fig. 6 (bottom left module). The theoretical transmissibility formula and the numerical model,considering the time delay,represent more realistic descriptions of the dynamics of the active vibration isolation system,from which the results can be better compared with the data from the experiment.

    3.4. Power analysis

    Fig.11 shows the time histories of the currents through the EM actuator and the rechargeable battery,together with the calculated power flow in an experimental case with the skyhook coefficient of csky= 40 N?s?m-1and excitation frequency of 5 Hz.

    The green dashed line in Fig. 11(a) represents the EMF divided by the circuit resistance Rtotal.Thus,the corresponding shaded area represents the energy-harvesting region according to Eq. (11). The EM actuator alternately operates in the power-harvesting and power-consuming modes when the actuator current falls inside and outside the shaded area, respectively. The red vertical dotted lines mark the intersection points of the actuator current (i.e.,the orange dashed line) and energy-harvesting region (i.e., green).These vertical lines divide the entire time history into ‘‘powerharvesting” and ‘‘power-consuming” regions, as shown in Fig.11(a).The blue dashed line shows the battery power calculated as the product of the battery current and voltage; the instantaneous positive and negative powers represent the powerharvesting and power-consuming processes,respectively.Provided that the battery current switches direction (charge and discharge)at a high frequency, the presented power in Fig. 11(a) is the average power over every 0.002 s (around four PWM periods). The points where the calculated instantaneous power equals zero coincide with the vertical red line partitions in the figure. In general,the actuator current in the power-harvesting region is within the green shaded area, and the instantaneous power of the battery is positive (energy-harvesting); conversely, the actuator current in the power-consuming region is outside the shaded area, and the instantaneous transient power of the battery is negative (energyconsuming).

    Fig. 11(b) specifically displays the battery current in the time domain corresponding to that in Fig. 11(a).The current in the battery (i.e., the gray solid line) switches direction at the frequency(i.e., 2 kHz) of the PWM control waves; the positive and negative currents within each PWM cycle, which represent the charge and discharge processes of the battery, respectively, have nearly equal magnitudes, while the current in the EM actuator (i.e., the orange dotted line)varies slowly at the vibration frequency(i.e.,5 Hz).The EM actuator current approximately profiles the battery current on one side because the actuator current alternatively connects to the battery in two opposite directions in a PWM cycle.

    Fig. 10. Comparison of the measured and target control forces in time domain (csky = 40 N?s?m-1, excitation frequency f = 5 Hz, sampling frequency fsample = 10 kHz). Exp:experimental.

    Fig. 11. Energy exchange between motor and rechargeable battery in time domain (csky = 40 N?s?m-1, f = 5 Hz): (a) actuator current and battery power flow; (b) actuator current and battery current with allocated windows indicating energy consumption and energy harvesting locations; and (c) enlarged windows showing details for energy consumption (①) and energy harvesting (②).

    Two representative time windows, denoted as ①and ②in Figs. 11(b) and (c), were selected from the power-consuming and power-harvesting regions. The variation in the measured battery current within one PWM cycle in the selected windows is shown in detail in the enlarged view in Fig. 11(c). The positive and negative currents correspond to the charge and discharge states of the battery,respectively.Both the positive and negative parts were flat and had nearly equal amplitudes. In window ①, the negative current lasted longer than the positive current(D1=42%),reflecting an energy-consuming effect.In window ②,the positive current lasted longer (D1= 54%) than the negative current, leading to an energyharvesting effect. The enlarged windows also show that the smoothed actuator current is approximately equal to the amplitude of the battery current, although the latter exhibits more significant fluctuations.

    Fig. 12 displays plots of the experimental and simulation relations of the control forces versus the relative velocities of the EM actuator obtained in two representative experimental cases, with Fig.12(a)csky=40 N?s?m-1,f=3 Hz and Fig.12(b)csky=40 N?s?m-1,f=7 Hz,which correspond to the energy-consumption and energyharvesting scenarios, respectively. The total damper force directly measured using the load cell included the EM and parasitic damping forces.The former represents a control force,while the latter is uncontrollable. The experimental EM control force was calculated based on the measured actuator current using Eq. (1). In general,the simulated EM force is consistent with the experimental EM force, demonstrating the accuracy of the numerical model presented in Section 3.3 that considers the time delay effect.

    The instantaneous power-harvesting and power-consuming zones depicted in Fig.4 are also highlighted in Fig.12.The elliptical control force–velocity loops in Figs. 12(a) and (b) pass through both the power-harvesting and power-consuming zones. Most of the elliptical force–velocity loop in Fig. 12(a) is located outside the green shaded area. According to Eq. (11), the average output powers (-P) in this case were estimated to be -80 and -59 mW for experimental and numerical results, respectively, demonstrating that the active EM actuator consumed energy overall. In contrast, the loop shown in Fig. 12(b) mainly lies in the green shaded area.The average output powers obtained from the experimental and numerical results were 8 and 3.6 mW, respectively.The positive output power suggests that the actively controlled actuator harvested energy overall.

    Fig. 12. Experimental results showing ranges of energy harvesting and energy dissipation. (a) Energy harvesting (csky = 40 N?s?m-1, f = 3 Hz); (b) energy consumption(csky = 40 N?s?m-1, f = 7 Hz). Sim: simulation; p1 and p2 match the two points marked in Figs. 13 and 14.

    Fig. 13 plots the theoretical, simulation, and experimental results of the average output power obtained in all cases. The theoretical curves were obtained using Eq. (19). The satisfactory agreement among the three results validates the efficacy of the theoretical and numerical models. In general, the vibration isolation performance improved with an increase in the skyhook damping coefficient csky, but the average output power decreased. The two points p1and p2in Fig. 13 correspond to 3 and 7 Hz, respectively,matching the force–velocity diagrams in Figs.12(a)and(b).

    Within the resonant frequency range of 6–10 Hz (the corresponding frequency ratio r ?[0.8, 1.4]), where excellent vibration control performance is required, active vibration isolation based on the skyhook algorithm could be successfully achieved in the energy-harvesting mode. However, in the low-frequency range(r < 0.7), the active isolation system operated in an energyconsuming mode. When the frequency ratio r > 2.07, although the theoretical result predicts a positive output power,the numerical and experimental results present an output power that is slightly less than zero owing to the extra power loss in the Hbridge circuit.

    Fig. 13. Average output power of the active vibration isolation system with skyhook control. Theo: theoretical.

    Thus, the self-powering feature was not realized in all of the experimental cases.This situation can be improved by minimizing the total resistance (Rtotal) of the circuit, which will enlarge the power-harvesting zone in Fig. 13. In addition, the superior active control performance is highly desirable in the resonant region,while outside the resonant region, the vibration isolation performance becomes less sensitive to csky. Hence, a lower cskyvalue can be adopted to achieve a tradeoff between energy and vibration control performance outside the resonant region.

    The foregoing power-balance discussion only considered the instantaneous power of the EM actuator. The additional power consumption of the sensors and MCU were not considered. However, only a small-scale structure was tested in this proof-ofconcept study. In large-scale structural control applications, the power consumption of the sensing and MCU units is negligible compared with the instantaneous vibration power from structures.

    3.5. Control performance

    Fig. 14. Transmissibility curves under skyhook control.

    Fig.14 shows the transmissibility curves of the actively isolated structure obtained in the theoretical and experimental studies under various conditions.The solid green line indicates the uncontrolled baseline case with only parasitic damping.The black dotted lines represent the transmissibility curves of the passive control group, with passive viscous dampers (csky= 20 and 40 N?s?m-1)installed between the structure and the ground. The red dashed lines show the theoretical curves of the ideal skyhook control as defined in Eq.(16),while the blue dash-dot lines represent the theoretical curves of the skyhook control, considering the time delay effect, as defined in Eq. (20). A comparison of these two groups illustrates the slightly negative impact of the time delay, particularly in the high-frequency range. Additionally, the two investigated points (p1and p2) are circled in pink.

    The experimental control performance corresponding to the two damping coefficients, csky= 20 and 40 N?s?m-1, satisfactorily agrees with the corresponding theoretical performance. This validates the successful active skyhook control performance. In general, active skyhook control can yield superior isolation performance over its passive counterparts. Considering csky= 40 N?s?m-1,the resonant peak became indistinct in the corresponding transmissibility curves.

    4. Conclusions

    This paper proposed an unprecedented self-powered active vibration control strategy to overcome the power supply bottleneck associated with conventional active vibration control techniques. The system design, working mechanism, power flow,control algorithm,and performance of the strategy were presented and discussed based on analytical, numerical, and experimental studies. The feasibility and effectiveness of the proposed system were examined by applying it to an active vibration isolation system. The results obtained in this study indicate that manipulating the duty cycles of PWM control signals according to the derived relation can not only enable accurate production of the target active control force but also allow the EM actuator to operate alternately in different power modes (power-harvesting or powerconsumption). Consequently, a truly self-powered active vibration isolation system was successfully achieved for the first time, and the classical skyhook vibration isolation could be realized without any external power supply to the EM actuator.

    Although the skyhook control algorithm was adopted in this study to illustrate the feasibility of the self-powered concept, the proposed strategy and setup present a generic solution that can be readily extended to other active vibration control applications with versatile active control algorithms, by simply modifying the sensing signals and updating the control algorithm code executed by the MCU. Therefore, the proposed self-powered strategy can have a profound impact on existing active vibration control techniques in a wide range of applications.

    Acknowledgments

    This work was supported by the Research Grants Council of Hong Kong through General Research Fund (GRF) projects(15214620 and PolyU 152246/18E), Research Impact Fund (PolyU R5020-18), and the NSFC/RGC Joint Research Scheme(N_PolyU533/17 and 51761165022).

    Compliance with ethics guidelines

    Jin-Yang Li and Songye Zhu declare that they have no conflicts of interest or financial conflicts to disclose.

    最近最新免费中文字幕在线| 久久久久久免费高清国产稀缺| 满18在线观看网站| 亚洲av美国av| 欧美午夜高清在线| 免费在线观看完整版高清| 欧美黑人欧美精品刺激| 亚洲精品美女久久av网站| 色综合站精品国产| 欧美黑人巨大hd| 在线看三级毛片| 两个人看的免费小视频| 免费在线观看视频国产中文字幕亚洲| 女性被躁到高潮视频| 亚洲精品中文字幕在线视频| 老熟妇仑乱视频hdxx| 欧美三级亚洲精品| 黄网站色视频无遮挡免费观看| 少妇 在线观看| 成人国产综合亚洲| 亚洲专区国产一区二区| 亚洲人成网站在线播放欧美日韩| 午夜激情av网站| 国产视频一区二区在线看| 亚洲专区中文字幕在线| 99精品欧美一区二区三区四区| 18美女黄网站色大片免费观看| 亚洲国产中文字幕在线视频| 又紧又爽又黄一区二区| 少妇被粗大的猛进出69影院| 母亲3免费完整高清在线观看| 精品午夜福利视频在线观看一区| 精品福利观看| 午夜福利一区二区在线看| 久久精品成人免费网站| 精品久久蜜臀av无| 久久精品亚洲精品国产色婷小说| 日韩精品免费视频一区二区三区| 日韩高清综合在线| 亚洲欧美日韩高清在线视频| 亚洲全国av大片| 国产一区二区在线av高清观看| 后天国语完整版免费观看| 亚洲人成网站高清观看| 久久午夜亚洲精品久久| 中文字幕最新亚洲高清| 丝袜在线中文字幕| 亚洲狠狠婷婷综合久久图片| 精品久久蜜臀av无| 国产精品乱码一区二三区的特点| 精品国产美女av久久久久小说| 亚洲黑人精品在线| 美女扒开内裤让男人捅视频| 一二三四在线观看免费中文在| 午夜a级毛片| 亚洲国产精品成人综合色| 成人三级做爰电影| 午夜激情av网站| 久热这里只有精品99| 免费人成视频x8x8入口观看| 午夜久久久久精精品| 女同久久另类99精品国产91| 亚洲精品美女久久av网站| 一级作爱视频免费观看| 成人精品一区二区免费| 美女大奶头视频| 男女之事视频高清在线观看| 精品久久久久久久久久久久久 | 激情在线观看视频在线高清| 1024手机看黄色片| 男人操女人黄网站| 老司机午夜十八禁免费视频| 欧美日韩亚洲国产一区二区在线观看| 国产单亲对白刺激| 国产又黄又爽又无遮挡在线| 精品久久久久久久人妻蜜臀av| 老司机深夜福利视频在线观看| 岛国在线观看网站| 999久久久精品免费观看国产| 日韩中文字幕欧美一区二区| 亚洲美女黄片视频| 国产精品,欧美在线| 国产精品精品国产色婷婷| 麻豆av在线久日| 日韩中文字幕欧美一区二区| 美女高潮喷水抽搐中文字幕| 给我免费播放毛片高清在线观看| 波多野结衣巨乳人妻| 嫩草影视91久久| 99国产综合亚洲精品| 亚洲成国产人片在线观看| 757午夜福利合集在线观看| 精品国产一区二区三区四区第35| 国产精华一区二区三区| 法律面前人人平等表现在哪些方面| 午夜久久久在线观看| 日韩欧美免费精品| 久久久久久大精品| 51午夜福利影视在线观看| 亚洲国产欧美一区二区综合| 中文字幕人妻熟女乱码| 国产成人欧美在线观看| 天堂影院成人在线观看| 成人欧美大片| 欧美精品啪啪一区二区三区| 妹子高潮喷水视频| 午夜福利18| 18禁国产床啪视频网站| 丝袜美腿诱惑在线| 欧美成狂野欧美在线观看| 欧洲精品卡2卡3卡4卡5卡区| 黑人操中国人逼视频| 色在线成人网| 高清毛片免费观看视频网站| 精品国产国语对白av| 天天躁狠狠躁夜夜躁狠狠躁| 俺也久久电影网| 欧美最黄视频在线播放免费| 啦啦啦免费观看视频1| 色精品久久人妻99蜜桃| 欧美一级a爱片免费观看看 | 欧美在线黄色| 一区二区三区精品91| 脱女人内裤的视频| 97人妻精品一区二区三区麻豆 | 麻豆成人午夜福利视频| 夜夜夜夜夜久久久久| 女人被狂操c到高潮| 日韩欧美国产在线观看| 成人一区二区视频在线观看| 欧美日韩精品网址| 麻豆久久精品国产亚洲av| 色在线成人网| 岛国视频午夜一区免费看| 精品国产乱码久久久久久男人| 久久性视频一级片| 精品欧美一区二区三区在线| 国产久久久一区二区三区| 国内精品久久久久精免费| 日本熟妇午夜| 亚洲精品国产区一区二| 男人舔女人的私密视频| 村上凉子中文字幕在线| 少妇被粗大的猛进出69影院| 淫秽高清视频在线观看| a级毛片在线看网站| 1024手机看黄色片| 国产激情久久老熟女| 午夜日韩欧美国产| 国产精品免费视频内射| 久久久久亚洲av毛片大全| 亚洲,欧美精品.| 国产亚洲精品久久久久5区| 成人手机av| 99热这里只有精品一区 | 一a级毛片在线观看| 久久精品影院6| 男人的好看免费观看在线视频 | 久久这里只有精品19| 国产精品 欧美亚洲| 中文资源天堂在线| 大型黄色视频在线免费观看| 久久久水蜜桃国产精品网| 国产精品久久视频播放| 99久久国产精品久久久| 日本在线视频免费播放| 91在线观看av| 一边摸一边做爽爽视频免费| 欧美在线黄色| 中文字幕人妻丝袜一区二区| 黄色视频,在线免费观看| 69av精品久久久久久| 精品熟女少妇八av免费久了| 国产单亲对白刺激| 日韩大尺度精品在线看网址| 少妇熟女aⅴ在线视频| 日本免费一区二区三区高清不卡| 88av欧美| 一个人观看的视频www高清免费观看 | 很黄的视频免费| 看黄色毛片网站| 老熟妇仑乱视频hdxx| 草草在线视频免费看| 香蕉丝袜av| 免费搜索国产男女视频| 久久草成人影院| 人人妻人人看人人澡| 国产亚洲精品久久久久久毛片| 在线视频色国产色| 成人免费观看视频高清| 一区二区三区精品91| 国产久久久一区二区三区| 不卡av一区二区三区| 最好的美女福利视频网| 国产欧美日韩精品亚洲av| 色精品久久人妻99蜜桃| 校园春色视频在线观看| 91九色精品人成在线观看| 老熟妇仑乱视频hdxx| 国产私拍福利视频在线观看| 国产精品 国内视频| 色av中文字幕| 色婷婷久久久亚洲欧美| 国产精品九九99| 亚洲av电影不卡..在线观看| 国产精品影院久久| 欧美zozozo另类| 国产精品 欧美亚洲| 757午夜福利合集在线观看| 日韩欧美 国产精品| 久久婷婷人人爽人人干人人爱| 国产精品九九99| 一本一本综合久久| 一本精品99久久精品77| 一级黄色大片毛片| 中文字幕人成人乱码亚洲影| 嫩草影院精品99| 日本一区二区免费在线视频| 夜夜躁狠狠躁天天躁| 国产亚洲av高清不卡| 一a级毛片在线观看| 日本 欧美在线| 精品久久久久久久久久久久久 | 免费在线观看完整版高清| 欧美人与性动交α欧美精品济南到| 老司机深夜福利视频在线观看| 亚洲成av片中文字幕在线观看| 少妇的丰满在线观看| 999久久久精品免费观看国产| 视频区欧美日本亚洲| 久久久精品国产亚洲av高清涩受| 啦啦啦韩国在线观看视频| 婷婷亚洲欧美| 一区二区三区高清视频在线| 国产精品久久久av美女十八| 免费高清在线观看日韩| 1024手机看黄色片| 成人18禁高潮啪啪吃奶动态图| 欧美国产精品va在线观看不卡| 亚洲国产精品999在线| 亚洲狠狠婷婷综合久久图片| 国产真实乱freesex| 高清在线国产一区| 国产精品98久久久久久宅男小说| 在线视频色国产色| 国产精品av久久久久免费| 久久久精品国产亚洲av高清涩受| 精品久久久久久久久久免费视频| 一区二区三区激情视频| 亚洲精品色激情综合| 青草久久国产| 啦啦啦观看免费观看视频高清| 精品国产超薄肉色丝袜足j| 久久久久久久久久黄片| 一区二区三区精品91| 黄片播放在线免费| 一区二区三区高清视频在线| 90打野战视频偷拍视频| 少妇的丰满在线观看| 亚洲成人久久性| 久久精品91无色码中文字幕| 亚洲国产精品合色在线| 淫秽高清视频在线观看| 久久 成人 亚洲| 丰满的人妻完整版| 亚洲国产精品久久男人天堂| 2021天堂中文幕一二区在线观 | 亚洲国产欧美日韩在线播放| 亚洲五月婷婷丁香| 一级黄色大片毛片| 亚洲五月天丁香| 国产免费男女视频| 叶爱在线成人免费视频播放| 精品高清国产在线一区| 美女高潮到喷水免费观看| 精品久久久久久久久久久久久 | 精品无人区乱码1区二区| 久久精品91蜜桃| 男女视频在线观看网站免费 | 亚洲成人精品中文字幕电影| 亚洲欧美激情综合另类| 此物有八面人人有两片| 欧美日韩一级在线毛片| 黄色 视频免费看| 午夜福利在线观看吧| 国产免费男女视频| 中文字幕另类日韩欧美亚洲嫩草| 91在线观看av| 国产乱人伦免费视频| videosex国产| 精品国内亚洲2022精品成人| www.999成人在线观看| 亚洲国产精品久久男人天堂| 国内揄拍国产精品人妻在线 | 国产精品1区2区在线观看.| 国产蜜桃级精品一区二区三区| 成人午夜高清在线视频 | 亚洲中文字幕一区二区三区有码在线看 | 桃红色精品国产亚洲av| 淫妇啪啪啪对白视频| 欧美三级亚洲精品| 亚洲精品国产精品久久久不卡| 久久这里只有精品19| 欧美性长视频在线观看| 男女做爰动态图高潮gif福利片| 俺也久久电影网| 日日夜夜操网爽| av天堂在线播放| 黄频高清免费视频| 亚洲av电影不卡..在线观看| 熟女电影av网| 91成年电影在线观看| 老司机福利观看| 日本黄色视频三级网站网址| 大型av网站在线播放| 一本综合久久免费| 日韩欧美免费精品| 免费在线观看视频国产中文字幕亚洲| 日本免费a在线| 中文资源天堂在线| 91av网站免费观看| 老司机深夜福利视频在线观看| 国产一区二区三区在线臀色熟女| 9191精品国产免费久久| av在线天堂中文字幕| 真人做人爱边吃奶动态| 国产成年人精品一区二区| av片东京热男人的天堂| www日本在线高清视频| 啦啦啦免费观看视频1| 高清毛片免费观看视频网站| 久久久久久久久中文| 美女午夜性视频免费| 免费看十八禁软件| 中文字幕av电影在线播放| 国产野战对白在线观看| 免费看美女性在线毛片视频| 99久久综合精品五月天人人| 亚洲电影在线观看av| 俄罗斯特黄特色一大片| 美女扒开内裤让男人捅视频| 国产一级毛片七仙女欲春2 | 久久青草综合色| 国产男靠女视频免费网站| 国产精品久久久久久人妻精品电影| 亚洲欧洲精品一区二区精品久久久| 999精品在线视频| 亚洲性夜色夜夜综合| 成人18禁在线播放| 日韩中文字幕欧美一区二区| 亚洲无线在线观看| 十分钟在线观看高清视频www| 久久国产精品影院| 亚洲av电影在线进入| 午夜久久久久精精品| 国产av在哪里看| 高清毛片免费观看视频网站| 精品高清国产在线一区| 天天躁狠狠躁夜夜躁狠狠躁| 一边摸一边抽搐一进一小说| 制服人妻中文乱码| 身体一侧抽搐| 免费看美女性在线毛片视频| 天堂影院成人在线观看| 婷婷精品国产亚洲av在线| 久久亚洲真实| 欧美最黄视频在线播放免费| 亚洲国产精品sss在线观看| 日韩高清综合在线| 热re99久久国产66热| 欧美黑人精品巨大| 国产麻豆成人av免费视频| 国产精品1区2区在线观看.| 天天添夜夜摸| 日本一本二区三区精品| 精品国产一区二区三区四区第35| 操出白浆在线播放| 婷婷精品国产亚洲av在线| 精品无人区乱码1区二区| 神马国产精品三级电影在线观看 | 久久国产亚洲av麻豆专区| 国产一区二区激情短视频| 成人欧美大片| 国产精品精品国产色婷婷| 亚洲一区二区三区不卡视频| 欧美成人性av电影在线观看| 婷婷精品国产亚洲av| 欧美成人一区二区免费高清观看 | 亚洲va日本ⅴa欧美va伊人久久| 18禁美女被吸乳视频| 欧美日韩瑟瑟在线播放| 日日干狠狠操夜夜爽| 国产精品国产高清国产av| 亚洲aⅴ乱码一区二区在线播放 | 99热只有精品国产| 可以在线观看毛片的网站| 亚洲中文av在线| 热re99久久国产66热| 黑丝袜美女国产一区| 国产熟女xx| 国产伦人伦偷精品视频| 欧美激情久久久久久爽电影| 中国美女看黄片| 久久精品91蜜桃| 最近在线观看免费完整版| 一区二区三区高清视频在线| 欧美色欧美亚洲另类二区| 女人高潮潮喷娇喘18禁视频| 色av中文字幕| 国产精品免费一区二区三区在线| 一级毛片女人18水好多| 久久久精品欧美日韩精品| 美国免费a级毛片| 亚洲七黄色美女视频| 国产乱人伦免费视频| 18禁裸乳无遮挡免费网站照片 | 99久久无色码亚洲精品果冻| 亚洲成人免费电影在线观看| 在线观看免费午夜福利视频| 村上凉子中文字幕在线| √禁漫天堂资源中文www| 少妇被粗大的猛进出69影院| 50天的宝宝边吃奶边哭怎么回事| 午夜福利免费观看在线| 国产亚洲精品一区二区www| 精品免费久久久久久久清纯| 久久国产精品影院| 99精品久久久久人妻精品| 午夜福利在线在线| 成人亚洲精品av一区二区| 国产av一区二区精品久久| 九色国产91popny在线| 日韩三级视频一区二区三区| 香蕉久久夜色| 国产精品 国内视频| 黄网站色视频无遮挡免费观看| 1024手机看黄色片| 人人妻人人澡欧美一区二区| www.精华液| 亚洲第一青青草原| 精品高清国产在线一区| 日日干狠狠操夜夜爽| 变态另类成人亚洲欧美熟女| 一进一出好大好爽视频| 黄片播放在线免费| 亚洲狠狠婷婷综合久久图片| 欧美不卡视频在线免费观看 | 黄片播放在线免费| 午夜日韩欧美国产| cao死你这个sao货| 亚洲中文字幕一区二区三区有码在线看 | 欧美黑人欧美精品刺激| 久久久久久久久中文| 男女之事视频高清在线观看| 欧美成人午夜精品| 99久久国产精品久久久| 99re在线观看精品视频| 国产在线精品亚洲第一网站| 亚洲狠狠婷婷综合久久图片| 成年版毛片免费区| 99在线视频只有这里精品首页| 久久欧美精品欧美久久欧美| 校园春色视频在线观看| 男女床上黄色一级片免费看| 国产亚洲精品综合一区在线观看 | 亚洲avbb在线观看| 波多野结衣高清作品| 色综合婷婷激情| 两个人视频免费观看高清| 欧美成人午夜精品| 久久久精品国产亚洲av高清涩受| 久久狼人影院| 国产在线精品亚洲第一网站| 听说在线观看完整版免费高清| 亚洲午夜精品一区,二区,三区| 91国产中文字幕| 国产亚洲av高清不卡| 免费在线观看黄色视频的| 国产亚洲精品第一综合不卡| 色尼玛亚洲综合影院| 亚洲精品美女久久av网站| 美国免费a级毛片| 久久天躁狠狠躁夜夜2o2o| 老汉色∧v一级毛片| 亚洲成a人片在线一区二区| 男人舔女人下体高潮全视频| 啦啦啦观看免费观看视频高清| 久久中文字幕人妻熟女| 少妇 在线观看| 免费在线观看黄色视频的| 丁香欧美五月| 91老司机精品| 少妇裸体淫交视频免费看高清 | 日韩精品青青久久久久久| 成人三级做爰电影| 免费高清视频大片| 欧美性长视频在线观看| 两性夫妻黄色片| 男女午夜视频在线观看| 亚洲天堂国产精品一区在线| 亚洲人成77777在线视频| 婷婷亚洲欧美| 在线观看日韩欧美| 国产又色又爽无遮挡免费看| 一级毛片女人18水好多| 亚洲精品中文字幕一二三四区| 成人特级黄色片久久久久久久| 无人区码免费观看不卡| 男女做爰动态图高潮gif福利片| 国产精品电影一区二区三区| 狠狠狠狠99中文字幕| 精品国产亚洲在线| 性欧美人与动物交配| 欧美激情 高清一区二区三区| 国产亚洲精品综合一区在线观看 | 一本精品99久久精品77| 亚洲狠狠婷婷综合久久图片| 精品少妇一区二区三区视频日本电影| 无人区码免费观看不卡| 男女做爰动态图高潮gif福利片| 日日爽夜夜爽网站| 国产精品久久久久久人妻精品电影| 国产精品亚洲一级av第二区| 一本久久中文字幕| 久久婷婷成人综合色麻豆| 黄片大片在线免费观看| 午夜成年电影在线免费观看| 男女做爰动态图高潮gif福利片| 在线播放国产精品三级| 久久精品影院6| 久久久久久久久中文| 在线天堂中文资源库| 一本综合久久免费| 久久国产乱子伦精品免费另类| 校园春色视频在线观看| 国产精品久久久人人做人人爽| 国产在线精品亚洲第一网站| 欧美又色又爽又黄视频| 欧美成人免费av一区二区三区| 久热这里只有精品99| 久久人妻av系列| 国产欧美日韩精品亚洲av| 中文字幕高清在线视频| 91成人精品电影| 久久人妻福利社区极品人妻图片| 婷婷亚洲欧美| tocl精华| 村上凉子中文字幕在线| 久久伊人香网站| 岛国视频午夜一区免费看| 精品高清国产在线一区| 国产亚洲精品久久久久5区| 一级黄色大片毛片| 亚洲黑人精品在线| 亚洲一区二区三区色噜噜| 精品无人区乱码1区二区| 日韩成人在线观看一区二区三区| 精品日产1卡2卡| 午夜福利一区二区在线看| 两个人看的免费小视频| 啦啦啦 在线观看视频| 日韩有码中文字幕| 国产男靠女视频免费网站| 99久久综合精品五月天人人| 久久99热这里只有精品18| 91老司机精品| 91成年电影在线观看| 天天一区二区日本电影三级| 久久天躁狠狠躁夜夜2o2o| 色哟哟哟哟哟哟| 99热6这里只有精品| 97人妻精品一区二区三区麻豆 | 国产成+人综合+亚洲专区| 免费搜索国产男女视频| 亚洲中文字幕日韩| 日韩有码中文字幕| 欧美av亚洲av综合av国产av| 国产久久久一区二区三区| 欧美黑人欧美精品刺激| 人人妻人人看人人澡| 两个人视频免费观看高清| 久久香蕉精品热| 一进一出抽搐动态| 亚洲国产精品sss在线观看| 在线播放国产精品三级| 久久久水蜜桃国产精品网| 香蕉久久夜色| 久久精品91无色码中文字幕| 国产成人欧美| 夜夜夜夜夜久久久久| 一区二区日韩欧美中文字幕| 男女那种视频在线观看| 亚洲人成77777在线视频| 欧美日韩精品网址| 亚洲成av人片免费观看| 男人舔奶头视频| 熟女少妇亚洲综合色aaa.| 亚洲精品色激情综合| 久久精品国产综合久久久| 亚洲黑人精品在线| 久久婷婷成人综合色麻豆| 成人国语在线视频| 91麻豆精品激情在线观看国产| 国产激情偷乱视频一区二区| 日韩欧美免费精品| 国产亚洲av高清不卡| 美女 人体艺术 gogo| www日本黄色视频网| 人人澡人人妻人| 亚洲九九香蕉| 午夜久久久久精精品| 老熟妇仑乱视频hdxx| 久久久久久久午夜电影| 国产片内射在线| 久久精品人妻少妇|