    An Intelligent IEQ Monitoring and Feedback System: Development and Applications

    2022-02-13 09:18:58YangGengZhongchenZhangJuanYuHongzhongChenHaoZhouBorongLinWeiminZhuang
    Engineering 2022年11期

    Yang Geng, Zhongchen Zhang, Juan Yu, Hongzhong Chen, Hao Zhou, Borong Lin,*,Weimin Zhuang*

    a School of Architecture, Tsinghua University, Beijing 100084, China

    b Key Laboratory of Eco Planning and Green Building, Ministry of Education, Tsinghua University, Beijing 100084, China

    c Beijing Key Laboratory of Indoor Air Quality Evaluation and Control, Tsinghua University, Beijing 100084, China

    d Architectural Design and Research Institute of Tsinghua University, Beijing 100084, China

    e Beijing Tsinghua Tongheng Urban Planning and Design Institute, Beijing 100085, China

    Keywords:Indoor environmental quality (IEQ)Sensors Continuous monitoring Graphical user interface Interactive feedback

    A B S T R A C T Indoor environmental quality (IEQ) significantly affects human health and wellbeing. Therefore, continuous IEQ monitoring and feedback is of great concern in both the industrial and academic communities.However, most existing studies only focus on developing sensors that cost-effectively promote IEQ measurement while ignoring interactions between the human side and IEQ monitoring. In this study,an intelligent IEQ monitoring and feedback system—the Intelligent Built Enviroment (IBEM)—is developed. Firstly, the IBEM hardware instrument integrates air temperature,relative humidity, CO2, particulate matter with an aerodynamic diameter no greater than 2.5 μm (PM2.5), and illuminance sensors within a small device.The accuracy of this integrated device was tested through a co-location experiment with reference sensors;the device exhibited a strong correlation with the reference sensors,with a slight deviation(R2 >0.97 and slopes between 1.01 and 1.05).Secondly,a wireless data transmission module,a cloud storage module,and graphical user interfaces(i.e.,a web platform and mobile interface)were built to establish a pathway for dataflow and interactive feedback with the occupants of the indoor environments. Thus, the IEQ parameters can be continuously monitored with a high spatiotemporal resolution,interactive feedback can be induced,and synchronous data collection on occupant satisfaction and objective environmental parameters can be realized. IBEM has been widely applied in 131 buildings in 18 cities/areas in China, with 1188 sample locations. Among these applications, we report on the targeted IEQ diagnoses of two individual buildings and the exploration of relationships between subjective and objective IEQ data in detail here. This work demonstrates the great value of IBEM in both industrial and academic research.

    1. Introduction

    People spend nearly 90% of their lifetime indoors [1]. Thus,indoor environmental quality (IEQ) directly affects human health and social wellbeing [2-4]. For example, long-term exposure to a raised indoor temperature and humidity level can result in more severe sick building syndrome (SBS) symptoms [5]. The intensity of SBS symptoms increase and working productivity decreases when the indoor air becomes stuffier[6].Logue and Price[7]from the Lawrence Berkeley National Lab studied the chronic health impact of indoor air pollutants in residences in the United States.They found that indoor air pollutants caused an annual loss of 400-1100 disability-adjusted life years (DALYs) per 100 000 persons, and that particulate matter with an aerodynamic diameter no greater than 2.5 μm(PM2.5)contributed most to the DALYs lost in this analysis.Another study by Xiang et al.[8]estimated that 5.7 billion and 190.1 billion USD losses were respectively attributable to short-and long-term indoor exposure to PM2.5of outdoor origin in urban China. These health and economic losses caused by poor IEQ have aroused significant concern and deep thinking on IEQ monitoring and control.

    Practical tools are needed in order to undertake measurements of IEQ efficiently and robustly.The traditional IEQ monitoring protocol consists of a large number of independent environmental sensors[9-11]for measurements such as air temperature,humidity, carbon dioxide (CO2), particulate matter (PM), air pollutants,illuminance, noise, and so forth. However, the total cost of these sensors is often overly high. Furthermore, their assembly is intensely invasive in real-life scenarios[12,13],which dramatically limits the popularity of IEQ measurements in the spatial dimension.In addition,these sensors only support local data storage,so IEQ measurement must be conducted on the spot or in the short term[14-16].Thus,traditional IEQ measurement tools are deficient in terms of spatiotemporal scale and data resolution. As a result, the previous understanding of IEQ characteristics has been partial and inaccurate.

    With the rise of the Internet of Things (IoT) and big data technologies in recent decades, considerable progress has been made on IEQ monitoring tools [17]. New technologies, such as sensor integration, wireless data transmission, and cloud service, are being introduced into the development of IEQ monitoring tools[18-20]. Ali et al. [21] developed an open-source platform for the integration of various IEQ sensors.This platform can support a flexible synchronization of massive and long-term IEQ measurements at a low cost. Kelly et al. [22] applied the IoT to establish an IEQ monitoring system in residential buildings that implements the wireless interconnection of sensors via ZigBee and Internet Protocol version 6 (IPv6). Parkinson et al. [23,24] developed a continuous IEQ monitoring system, SAMBA, based on a wireless sensor network. SAMBA provides a more comprehensive solution for understanding the performance of indoor environments,consisting of both a low-cost suite of sensors and a web platform for IEQ rating and analysis. These new tools have significantly enhanced the efficiency of IEQ measurement. More importantly, they provide the opportunity for IEQ data collection on a broader spatiotemporal scale and with more satisfactory resolution.

    However, objective IEQ monitoring alone is not enough to achieve an excellent indoor environment. It is also necessary to open up a path for IEQ information interaction with occupants. The occupants of an indoor environment often desire to know the objective IEQ conditions in their surrounding areas[25]; furthermore, researchers in the field need to listen to the opinions of occupants in order to create a better indoor environment [26]. Unfortunately, although many researchers have conducted objective measurements and subjective surveys of IEQ in their studies, it is difficult to synchronize objective and subjective data within a broad spatiotemporal scale [27-30]. In other words, the actual IEQ conditions at the exact time and location the survey occurred are unknown, and people are surveyed without understanding objective IEQ results. This defect makes further studies on the correlation between IEQ parameters and occupant satisfaction in real-life scenarios impossible.In sum, the existing tools cannot achieve the simultaneous data collection of objective IEQ data and occupant opinions, nor do they permit information interaction between indoor environmental data and occupants.

    Therefore,the primary goal of this study was to develop an IEQ monitoring device that consists of multiple sensors with low cost,high accuracy,and remote transmission.Based on the hardware of this IEQ device, we also aimed to build an intelligent IEQ system software that includes a cloud database and platform. The proposed system is expected to not only achieve long-term continuous IEQ monitoring but also support simultaneous information interaction and occupant feedback.

    The remainder of this paper is organized as follows:

    ●Section 2 provides a detailed description of the technology

    from both the software and hardware sides.

    ●Section 3 examines the sensor performance based on a field experiment.

    ●Section 4 presents the technology application with a few examples.

    ●Section 5 discusses a comparison with other counterparts and the limitations of this study.

    2. Development of the intelligent built environment monitor

    Our group has been developing the Intelligent Built Environment Monitor(IBEM)since 2014.Thus far,IBEM is still undergoing continuous improvement and upgrading. This section introduces the whole architecture of IBEM, including both hardware and software.

    As shown in Fig. 1, IBEM comprises five parts—an integrated sensor, a cloud server, a database, a web platform, and a mobile interface—that are connected and finally evolve into a pathway for dataflow. IEQ data (i.e., air temperature (temp), relative humidity (RH), CO2, PM2.5, and illuminance) are collected by the integrated sensor and transmitted to the cloud server through the third-generation mobile communication technology (3G), 4G,or Wi-Fi. After receiving the data, the cloud server saves it into the database. Then, the server transfers the data to the web platform and mobile interface for tracking, visualization, and analysis when needed. On the web platform, people can examine the running status of IBEM, see historical IEQ data, and download data for further analyses.On the mobile interface,the IEQ information is provided to occupants more directly,such as in the form of an objective value and assessment score of the real-time IEQ conditions and optimization suggestions to address poor IEQ factors.

    Meanwhile, people can express their opinions and provide satisfaction ratings on the mobile interface regarding thermal comfort, air quality, lighting, acoustic quality, and overall environment.These subjective votes are uploaded to the cloud server and immediately fused with the corresponding objective IEQ data that was recorded at the same time the ratings were provided.This is the key to achieving the synchronous collection of objective and subjective IEQ data.

    Based on IBEM, multiple IEQ parameters can be monitored using only one instrument, which helps solve the spatiotemporal sampling problem at a low cost. More importantly, this system connects the indoor environment with its occupants and breaks the information asymmetry between them.The following two subsections introduce the detailed technical information of IBEM.

    2.1. Hardware

    The IBEM hardware mainly comprises environmental parameter sensors, which are the foundation of IEQ data collection. In order to reduce the cost and improve the convenience of environmental monitoring, a sensor integration design is adopted in this study. However, considering the cost and size, it is impractical to include all IEQ sensors in one instrument.Therefore, after deliberations on the importance of each IEQ parameter and the need for long-term monitoring, five sensors were eventually chosen: temp,RH, CO2, PM2.5, and illuminance. Table 1 lists the selected sensors’information(i.e.,supplier,measurement principle,range,and accuracy). The manufacturer certification periods of all sensors are more than three years.

    Two caveats need to be explained:

    (1) Sensors of chemical pollutants, such as formaldehyde or total volatile organic compounds(TVOCs),were not integrated into the IBEM. Although the costs of these sensors are relatively small,low-cost TVOC sensors lack specificity and formaldehyde sensors lack accuracy at appropriate levels, limiting their applicability in this study. Furthermore, the need for long-term continuous monitoring of chemical pollutants is not specially required in Chinese standards [31-33]. The standard measurement protocol is a sampling test under certain conditions rather than long-term monitoring.

    Fig. 1. The system architecture of IBEM. TSDB: time-series database. TSPB: time-series database.

    Table 1 Information on the IEQ sensors.

    (2)Noise level was not included,even though acoustics have an impact on human perceptions of IEQ. This is one of the defects in our hardware development, but we still have two considerations:Firstly, noise standards [34-36] focus more on background noise and less on speech.For example,according to the Chinese national standard on noise [36], a room’s acoustic performance should be assessed when the outdoor noise is at its maximum. Furthermore,the room should be unoccupied, the heating, ventilation, and air conditioning (HVAC) system should be running, and the windows should be closed during the noise measurement. Therefore, there are no continuous sampling requirements for noise level over timeframes[24],and a one-time noise test under the most adverse conditions is adequate in many cases. Secondly, unlike other IEQ parameters,there are nearly no immediate control means or technologies for the acoustic environment in most buildings.Therefore,although we could obtain the real-time noise level, the value of these data for improving the operating acoustic performance is negligible. From this perspective, the continuous monitoring of noise levels seems less valuable in comparison with other parameters.

    In addition to sensors, the hardware includes other functional modules: a data transmission module, a data storage module(backup), a power module, and a display module. All of these are integrated into one device, as shown in Fig. 2. After years of research,the integrated device has gone through several upgrades and renovations. As a result, the latest version of the device is a palm-sized round box with a diameter of 125 mm and a height of 40 mm, which can be placed on desks in real-life measurement scenarios.

    Fig. 2. (a) The entire development process of IBEM with different versions; (b) the internal structure of the IBEM device, including sensors, data transmission module, data storage module, power module, and display module. SIM: subscriber identity module; SD: secure digital.

    The data transmission module can upload IEQ data to the cloud via 3G,4G,or Wi-Fi at predefined intervals(e.g.,every 1 or 5 min).3G or 4G transmission is automatically achieved by the subscriber identity module (SIM) card pre-embedded inside the device,without any additional operations on site. Alternatively, Wi-Fi transmission requires users to connect the device to existing Wi-Fi in several steps that take less than 2 min. These two signals can be used as double insurance to guarantee wireless data transmission in most cases.Furthermore,the data transmission module has a self-recovery function that recovers the connection automatically after a temporary network interruption.This function significantly improves the data transmission reliability in long-term monitoring.

    The data storage module mainly provides a backup of data storage for cases in which wireless data transmission cannot be achieved. IEQ data can be stored locally in a micro secure digital(microSD)card,which generally accommodates the amount of data from more than one year of continuous monitoring.

    The power module includes an external power interface (universal serial bus (USB) Type C) and one button battery for backup.The designed electrical parameters are 5 V direct current(DC)and 2 A as input. Typically, the device is powered by external electricity. However, when the external power supply shuts down temporarily,the button battery can be used as a short-term power supply that can generally provide continuous power for one week.

    The display module is designed for the visualization of real-time IEQ data and the status of network connections. An light emitting diode (LED) screen is installed on the front of the device, which can be turned on by pressing the button and automatically goes off after 15 s to conserve energy.

    Given its many sensors and modules, it is a major challenge to minimize interference for the integrated device—especially the influence of heat dissipation on the measurement accuracy of the air temperature and relative humidity sensors.Solutions were considered from three aspects and adopted to solve this problem.Firstly,air temperature and relative humidity sensors are installed at the windward position(i.e.,the edge of the mainboard closest to the external environment), so the airflow passes through them first. Secondly, the rated power of each module is controlled at below 1 W to reduce heat dissipation. Thirdly, the distance between the primary heat sources and the sensors has been designed to be as far as possible. For example, the Wi-Fi module is placed on the opposite side of the mainboard at the farthest distance from the air temperature and relative humidity sensors.Based on the above considerations, the measurement accuracy of IBEM is ensured. The performance test and validation results are further presented in Section 3.

    2.2. Software

    The software design of IBEM consists of two main parts:①data transmission and storage (i.e., the cloud server and database) and②data presentation and human-computer interaction (i.e., the web platform and mobile interface).

    Data transmission and storage: The whole architecture is developed based on the software-as-a-service (SaaS) concept, as shown in Fig.3.Firstly,Nginx load-balancing technology is applied to access the multi-source data. Secondly, the Apache Tomcat 8.0 server and Linux operating system are adopted. JavaEE Spring is used as the server programming framework. The servers use the same application programming interface (API) under the unified standard to make it convenient to find data.Thirdly,different databases store different data types to ensure efficient reading and writing; these databases include a time-series database (TSDB)for dynamic IEQ data, MySQL database for static information data,and MongoDB database for subjective survey data. In addition, a master-slave backup work mode is adopted in all databases, and all the data are synchronized through the intranet to ensure data security.

    Data presentation and human-computer interaction: Both the web platform and the mobile interface were developed to establish an information ‘‘bridge” or pathway between the indoor environment and its occupants, as shown in Fig. 4. The web platform is open to professionals and data analysts for data visualization and downloads,while the mobile interface is mainly designed for the building occupants to assess the IEQ conditions and rate their opinions. People can easily access the mobile interface by using their smartphones to scan the quick response (QR) code attached to the IBEM monitoring device placed nearest to them.Fig. 4(b) shows several primary functions of the mobile interface,which are further illustrated below.

    Fig. 3. The framework of data transmission and storage.

    Fig. 4. Data presentation and human-computer interaction.

    Occupants can see the real-time IEQ parameters and their ratings. The rating represents an assessment of the criterion-based compliance performance of the IEQ parameter. The measurement results of specific parameters are checked against the compliance criteria drawn from the relevant national or international standards (Table 2) [33,36-39] to determine the ratings. When calculating the real-time rating of one IEQ parameter, the IBEM measurements within the past 1 h period are considered. That is,the rating is calculated based on the percent of measurement results within the compliance range in the last hour: The rating X represents X% of the measurement results in compliance.

    Finally, the overall IEQ index with a centesimal grade is calculated based on the weighting scheme (Table 3). For thermal comfort, the weight is set to 0.30 (0.18 for temperature and 0.12 for humidity),which is generally consistent with the previous settings[12]. A higher weight (0.40) is put on indoor air quality (IAQ),compared with other studies (0.14-0.36), because Chinese people usually pay more attention to IAQ, and their satisfaction with IAQ is relatively low, according to our previous study [40]. More specifically, we set the weight of CO2to 0.24 and the weight of PM2.5to 0.16. The weight value for CO2concentration is higher because this measurement can reflect the overall ventilation performance and is often used as a comprehensive indicator for IAQ evaluation. For lighting, the weight is set to 0.15, which is slightly lower than in other studies(0.16-0.29).This is because the indoor lighting environment generally reaches the standard, according to a large-scale measurement of green buildings in China [41]. Thus,we lowered the weight of illuminance to make the differentiation of the IEQ index more prominent and to reflect the problems of other IEQ factors to a greater extent. In regard to acoustics,although IBEM cannot measure noise level yet, the weight of acoustics is still kept in order to ensure the integrity of the IEQ evaluation;however,its weight is lowered to 0.15,compared with other studies(0.18-0.39).At present,we assume a maximum score for acoustics. In the future, when a noise sensor is added to the IBEM device, the weight of noise level will be adjusted, and the score for acoustics will vary according to the measured data.Finally, it should be mentioned that the weighting scheme given in this paper is just an example, and it will be revised as the research goes further.

    Table 2 The compliance range for each IEQ parameter.

    Historical IEQ data is also available on the IBEM mobile interface.However,unlike the corresponding function on the web platform, a historical data query on the mobile interface will only support a recent short period (less than one day). The purpose of this design is to reduce the interface’s response time and ensure a good user experience.

    Table 3 The weighting scheme for IEQ index calculation.

    For IEQ factors with poor performance, the mobile interface provides specific suggestions to help occupants make appropriate adjustments. For example, the interface suggests that the occupants turn on air purifiers when the IAQ is very bad. More importantly,a voting module is developed based on the mobile interface.People can submit their perceptions or level of satisfaction with each IEQ factor after learning about the actual IEQ parameters.These votes are matched with the objective IEQ parameters monitored by the IBEM device for that particular time period and place,and the combined data is uploaded and saved in the database. In this way,subjective and objective IEQ data can be collected simultaneously,thereby overcoming the disadvantage in traditional retrospective surveys of blindness to objective IEQ conditions.That is,it is possible to know how different IEQ conditions affect people’s perceptions in actual buildings. This result can help researchers identify the most satisfactory IEQ conditions for a certain space.Such information is the key to the on-demand provisioning of environmental control. Another feature of this vote collection method is that it can accept ratings from building occupants passively,instead of conducting surveys actively (which may make people annoyed). However, this approach may also cause a bias toward dissatisfaction because people are more likely to vote (i.e., complain) when they feel uncomfortable, rather than voting when the IEQ performance is satisfactory. This issue needs to be addressed, although more analyses are required for verification.In this paper,we will not discuss the issue of possible bias further.

    3. Performance test based on a limited field evaluation

    Before use, the IBEM devices are first calibrated in a testing chamber by the National Institute of Metrology (see Section S1 in Appendix A). In order to describe the IBEM performance after authoritative calibration, this section presents a limited field evaluation in a controlled office. The performance and accuracy of the IBEM monitoring devices were tested based on the co-location strategy with several commercial sensors (i.e., reference sensors). More information on the reference sensors is provided in Table 4 [42]. These reference sensors were chosen for comparison because they were widely used in both industry and academic researches[43,44].All the reference sensors were within the manufacturer certification period,ensuring adequate accuracy.

    Co-location of both IBEM devices and their commercial equivalents was done in five locations in an office with two floors. These five locations were selected to collect data from very different environments,which ensured that the parameter range during the test was as wide as possible.Data collection occurred at 5 min intervals over two days for both the commercial and IBEM devices.The averaging time was 10 min for each measurement. Fig. 5 shows the office floor plan and the placement of devices for co-location testing.All devices were placed on desks at a height of 0.75 m.

    In the office space, a variable refrigerant volume air conditioning system and humidifier were used for thermal environment(i.e., air temperature and RH) control. Electric shading blinds and LED lights with adjustable luminous flux and color temperature were used for lighting control. Mechanical ventilation equipment with high-efficiency filters (the minimum efficiency reporting value (MERV) of the filters was 15) was used to provide outdoor air for CO2concentration control, and air purifiers were used for PM2.5concentration control. Furthermore, to create conditions with high CO2and PM2.5concentrations during the test, dry ice and incense were used as the respective sources of CO2and PM2.5. During the experiment, the room was unoccupied, and we created considerably different IEQ conditions with an air temperature varying from 15 to 27°C,RH varying from 20%to 60%,illuminance varying from 0 to 700 lx, CO2concentration varying from 400 to 2000 parts per million(ppm),and PM2.5concentration varying from 10 to 200 μg·m-3. As a result, the IEQ conditions were broad enough to simulate most scenarios in actual buildings.

    IEQ monitoring data from the IBEM devices and their commercial counterparts were compared, and linear correlations are shown in Fig. 6. The IBEM and HOBO data loggers revealed strong correlations for temperature and RH readings throughout the test(Figs. 6(a) and (b); R2>0.99 and slopes between 1.01 and 1.02).The average deviation was 0.3 °C for temperature and 0.9% for RH.CO2and PM2.5concentration measurements were also strongly correlated between the IBEM devices and their counterparts(Figs. 6(c) and (d); R2>0.97 and slopes between 1.01 and 1.05),albeit with some scatter. The average deviation was only 25 ppm for CO2concentration and 7 μg·m-3for PM2.5concentration. For illuminance, the IBEM devices showed strong correlations with the TESTO sensors (Fig. 6(e); R2>0.98 and slope = 1.01), and the average deviation was less than 11 lx. These test results validate the measurement accuracy of the IBEM devices.

    It should be noted that the above experiment tested the shortterm performance of IBEM under different IEQ conditions.In terms of long-term performance, IBEM can perform self-calibration for CO2concentration and illuminance in most buildings because the baseline values of these measurements are roughly constant over time. For example, the baseline of CO2concentration is 400 ppm(outdoor value). If a room is unoccupied and well-ventilated for a long time, the indoor CO2concentration should decrease to 400 ppm. Similarly, the baseline of illuminance is 0 lx (totally dark). If the room is unoccupied at night and all lights are off,the indoor illuminance should be 0 lx. The self-calibration algorithm automatically compares the minimum measured value in a certain period with the baseline value and then removes the offset.However, if a building has no long periods of non-occupancy, it is difficult to determine the IEQ parameter baseline. Under such circumstances, the self-calibration method is not valid, and it is necessary to call back the monitoring devices for manual calibration.The baselines for temperature,RH,and PM2.5concentration are not constant over time due to the influence of outdoor weather and other factors. Thus, the calibrations for these measurements over the long term must generally be manual.Our study calls back each monitoring device for manual calibration and maintenance at least once a year. Furthermore, we entrusted a third-party detection institution to conduct high-frequency data acquisition tests under an extreme environment,demonstrating the long-term operational reliability of IBEM.

    Table 4 Information on the reference sensors.

    Fig. 5. Placement of IBEM and commercial devices for co-location testing.

    Fig. 6. Comparisons between IBEM devices and their commercial counterparts: (a)-(c) HOBO; (d) TONGDY; and (e) TESTO.

    4. Applications and results

    The IBEM is being applied in many actual buildings in China.By the end of 2020,the devices and systems had been deployed in 131 buildings in 18 cities/area, covering four climate zones, including severe cold, cold, hot-summer-cold-winter (HSCW), and hotsummer-warm-winter(HSWW)zone.The measured buildings also included a variety of types, such as office (48%), shopping mall(13%), school (9%), hospital (8%), hotel (6%), residence (11%), and others (5%). Fig. 7 shows the distribution of geographic locations and types of monitored buildings.

    The selection principle for the number and location of sensors in each building is illustrated in Section S2 in Appendix A,which considers the building types, areas, floors, room types, orientations,and other factors. Thus far, a total of 1188 sensor locations have been accumulated.

    At each sample location, IEQ parameters are continuously monitored for a whole year or for at least two weeks in each season, with a data collection interval of 1 or 5 min. The average online rate is nearly 90%, except for artificially unplugged devices.In addition, occupant feedback from the area near each sample location is collected via the mobile interface of IBEM. As a result,an IEQ database with a broad spatiotemporal scale and relatively fine resolution has been established. The data amount exceeds 1.09 TB, including more than three billion records of IEQ parameters and 2425 building occupant votes fused with objective IEQ data from the same time period and location.

    Based on such a large-scale IEQ database, many analyses have been conducted.Firstly,the macro characteristics of IEQ in Chinese buildings were revealed, and overall poor IEQ performances were observed.For example,the imbalance between supply and demand in thermal environment control was a significant problem. During winter, overheating in the cold zone (i.e., ‘‘supply” >‘‘demand”)was common, while heating was insufficient (i.e., ‘‘supply” < ‘‘demand”) in the HSCW zone. This work has been published in Building and Environment[41].Secondly,detailed analyses and targeted diagnoses of IEQ performance in certain individual buildings were carried out according to the spatiotemporal and dynamic features of IEQ.This work can help building operators to improve IEQ practically. Thirdly, correlations between subjective and objective IEQ data were studied,providing assistance to researchers in determining what IEQ parameters are most satisfactory and what occupants’actual demands are for IEQ control.

    Since a report on the first application has already been published, the first application will not be discussed further here.Instead, the following sections provide a few examples of the second and third applications.

    4.1. Targeted IEQ diagnosis of individual buildings

    Based on long-term continuous IEQ monitoring in multiple spaces within one building, we conducted targeted IEQ diagnosis,which can tell building operators when and where IEQ performances are inadequate. Here, we present two examples of IEQ diagnosis with the help of IBEM, one in an office and the other in a hospital.

    4.1.1. Case 1: Thermal environment diagnosis in an office building

    Fig. 7. Distribution of geographic locations and types of monitored buildings.

    The selected office building is located in Tianjin(a cold zone).It has five floors, and the total floor area is 5700 m2. We deployed a total of ten IBEM devices on the ground floor, intermediate floor,and top floor. Open-plan offices and private offices with various orientations were chosen as the main measured spaces. Continuous monitoring lasted for a whole year. Data from July, 2017 are chosen here to diagnose the indoor thermal performance in summer, as shown in Fig. 8.

    For each space,all data within the same hour from all workdays in July were gathered.These data were then classified into different temperature range partitions,and the monthly average proportion of each partition within the same hour was calculated.Finally,the daily variation of the temperature partition proportion within each hour was presented in a stacking bar chart.In this way,the results represent the comprehensive indoor thermal environment characteristics over a whole month, instead of randomly selecting one day for analysis. Furthermore, this method allows the variation and distribution features to be seen clearly, rather than providing a single index on average.

    As shown in Fig. 8, the private office in the east and the openplan office in the south had a good thermal performance.However,the indoor air temperatures in the open-plan office in the north and the private office in the west were often above the comfort zone (>28 °C) during the daytime. For the private office in the west, the thermal problem was much worse in the afternoon due to intense sunlight from the setting sun coming through the glass curtain wall. In addition, the lobby entrance hall was always hot during the daytime even though the air conditioning system was working, due to frequent openings of the front door. These results from the thermal environment diagnosis were fed back to the building operators, and the corresponding retrofits were put underway to enhance the occupants’ thermal comfort.

    4.1.2. Case 2: Indoor air quality diagnosis in a hospital building

    During the coronavirus disease 2019 (COVID-19) epidemic,IBEM was used in hospital buildings for real-time IEQ diagnosis and early warning of indoor environmental risks. CO2and PM2.5concentrations were the critical parameters of concern: ①CO2concentration reflects the ventilation performance; and ②PM2.5concentration reflects indoor air cleanliness and the purification effect of the filtration system.

    One hospital from Wuhan (in the HSCW zone) is selected here to show the IAQ diagnosis results based on IBEM.The floor area of the building is 22 154 m2. A total of 24 IBEM devices were deployed in almost all types of rooms with different functions,including inpatient wards, emergency treatment rooms, consulting rooms, pharmacies, offices, nurse stations, locker rooms,lounges, and aisles. Continuous IEQ monitoring at 5 min intervals began on 14 March and continued to 29 April 2020. Due to the high spatiotemporal resolution of the data collection, an IAQ dynamic field at each moment was obtained based on the spatial interpolation method. This study used triangulation with linear interpolation to assign values to the empty areas between sample locations.

    Fig. 9 shows the IAQ dynamic field of the hospital within one typical day.Screenshots of the field are only shown for times when poor air quality was found during the daytime. It was found that inadequate ventilation (high CO2concentrations) mainly occurred in the inpatient wards. However, the problem of insufficient air purification (high PM2.5concentrations) could occur in almost every space, such as in contaminated zones (i.e., inpatient wards,etc.), semi-contaminated zones (i.e., treatment rooms, aisles,etc.), and clean zones (i.e., locker rooms, offices, etc.).

    According to the diagnosis results for the IAQ in the hospital, it is possible to pinpoint where and when the problems arise and thus improve the corresponding ventilation and purification strategy in a timely manner. Therefore, IBEM provides technical support for preventing and controlling infection risks from indoor air aerosols in hospitals.

    Fig. 8. Targeted thermal environment diagnosis for an office building.

    Fig.9. A dynamic diagnosis of the IAQ field of a hospital building(because graphic interchange format(GIF)animation cannot be displayed in this figure,the measurements from one day and a few screenshots of certain moments were selected for examples).

    4.2. Correlations between subjective and objective IEQ data

    Previous studies have explored human perceptions of and responses to IEQ parameters through a series of experiments in climate chambers or simulated spaces [45]. However, the relationship between subjective perceptions and objective parameters in real-life scenarios is often different from that in climate chambers or simulated spaces because people’s activities and behaviors are not controlled in actual buildings. Thus, it is necessary to study building occupants’ satisfaction and demands on IEQ parameters under natural conditions.

    Based on IBEM and its function of information interaction and feedback via the mobile interface,we have collected 2425 building occupants’satisfaction votes on IEQ,which were matched with the environmental parameters at the relevant times and locations.Occupant votes use a seven-point scale with ‘‘+3” indicating‘‘very satisfied” and ‘‘-3” indicating ‘‘very dissatisfied.” Distributions of occupant satisfaction under different IEQ conditions were analyzed and compared.The findings presented below show how indoor air temperature and CO2concentration each affect occupant satisfaction.

    4.2.1. How does indoor air temperature affect thermal satisfaction?

    Differences in climate and HVAC systems between northern and southern China can influence thermal experiences and preferences.Thus,the collected occupant votes were split into two parts:Occupants from the severe cold and cold zones were gathered to represent the northern group, while occupants from the HSCW and HSWW zones represented the southern group.

    The thermal satisfaction votes of these two groups under different indoor air temperature conditions during summer and winter were compared, as shown in Fig. 10. A statistical test (the Wilcoxon-Mann-Whitney test) was conducted, and the P values between the two data groups were calculated. If the difference was statistically significant, it was marked with an asterisk(P < 0.05) or two asterisks (P < 0.01). Furthermore, the percentage of satisfied occupants(i.e.,votes from‘‘0”to‘‘+3”)was calculated at each temperature partition and compared with the predicted result according to the predicted mean vote(PMV)-predicted percentage dissatisfied(PPD)model for thermal comfort[46].The predicted percentage of satisfied occupants was calculated based on several assumptions: ①The mean radiant temperature equaled the air temperature; ②the airspeed was below 0.2 m·s-1; ③the metabolic rate of the occupants was 1.0 Met(1 Met=58.2 W·m-2);and ④the clothing insulation in summer and winter was 0.5 and 1.0 Clo (1 Clo = 0.155 m2·K·W-1), respectively.

    During summer, 24-26 °C was the most satisfactory thermal condition for both the northern and southern groups. However,the northern group had a weaker acceptance of cooler conditions than the southern group. When the indoor air temperature was below 22 °C, the thermal satisfaction of the northern group dropped more sharply than that of the southern group (P < 0.05 when the temperature was within 20-22 °C; P < 0.01 when the temperature was below 20 °C). Compared with the PMV-PPD model,the percentage of satisfied occupants in the northern group was below the model-based prediction when the air temperature went below 22 °C. This result indicates that buildings in northern China should avoid the overcooling problem in summer for thermal environment control. Otherwise, occupant satisfaction will decrease dramatically, along with the problem of energy waste.

    In winter, thermal satisfaction from the southern group varied more smoothly with air temperature, and their relationship was consistent with the PMV-PPD model. However, due to living in an environment with central heating for years, occupants from northern China were pickier about thermal conditions in winter.As long as the air temperature was not within the range of 20-26 °C, the actual thermal satisfaction from the northern group would decrease significantly—a result that was much lower than that of the southern counterpart and the PMV-PPD prediction results under the same conditions(P<0.05 when the temperature was below 18 °C; P < 0.01 when the temperature was within 18-20 °C and above 26 °C). Such a result indicates that building occupants in northern China have a narrower range of adaptation to the thermal environment in winter. Therefore, it is challenging to achieve high satisfaction in temperature control among northern Chinese occupants during the winter.

    4.2.2. How does indoor CO2concentration affect air quality satisfaction?

    Fig. 10. Relationship between indoor air temperature and occupant thermal satisfaction. Blue represents the Northern group (severe cold/cold zone), red represents the southern group (HSCW/HSWW zone), and green represents the predicted result of the PMV-PPD model; significance test: *P < 0.05 and **P < 0.01.

    Before studying the relationship between CO2concentration and occupant satisfaction with air quality, it is first necessary to distinguish how buildings are ventilated. Buildings in China are generally categorized into types A and B, according to different ventilation types. Type A refers to buildings whose windows can be opened for natural ventilation, while type B refers to buildings that use mechanical ventilation throughout the year.

    Fig. 11 shows the occupant votes for indoor air satisfaction at different CO2concentrations and gives a comparison between building types A and B, tested with the Wilcoxon-Mann-Whitney test. It was found that the average IAQ satisfaction at different levels of CO2concentration varied within a small range,regardless of whether the occupants were in building type A or B.The average satisfaction score was always above zero at any level of CO2concentration. However, the votes extended to ‘‘-3” for all data groups, which suggested that a substantial minority always considered the air quality unacceptable,regardless of the objective IAQ performance. This result indicates that people are not very sensitive to CO2concentration, and it is difficult to increase their subjective satisfaction by improving the objective performance.From the perspective of energy conservation, it is unnecessary to maintain CO2concentration at a very low level,as long as the limit of 1000 ppm is not exceeded. However, the occupants in building type A seemed to have a lower acceptance for relatively high CO2concentrations than the occupants in building type B. When the CO2concentration was above 800 ppm, the occupant satisfaction with air quality in building type A was significantly lower than that in building type B (P < 0.01).

    5. Discussion

    The large-scale applications and results from the case studies provided above have demonstrated that IBEM can be used efficiently for IEQ monitoring, feedback, diagnosis, and improvement.However,similar IEQ monitoring tools and systems can be found in other studies. In order to clearly show the advantages and disadvantages of different systems, this section compares their performance in five aspects: diversity of sensors, integration,extendibility, data platform, and feedback and interaction, as shown in Table 5 [19-21,23,24,47-52].

    ●Diversity of sensors: In this aspect, IBEM does not perform well, as it only includes sensors for air temperature, RH, CO2,PM2.5, and illuminance, without acoustics and other air quality parameters. Some other systems selected more sensors for more comprehensive IEQ monitoring. For example, SAMBA[23,24]also measures globe temperature,airspeed,sound pressure level,CO,formaldehyde,and TVOCs,besides the above five parameters in IBEM. More extensively, the IEQ system introduced by Liu et al. [51] and Dai et al. [52] even monitors occupants’ actions in terms of opening/closing windows and operating the parameters of the mechanical ventilation system,both of which have significant influences on IEQ.

    Fig. 11. Relationship between indoor CO2 concentration and occupant air quality satisfaction. Blue represents occupant votes from building type A, and red represents occupant votes from building type B; significance test: **P < 0.01.

    Table 5 Comparison between IBEM and other intelligent IEQ monitoring tools and systems.

    ●Integration: Except for a small minority of studies [51,52] that directly use multiple individual market devices for IEQ monitoring, most systems—including the IBEM—have developed a hardware solution that integrates a suite of sensors into a single‘‘box” for low-cost and high-efficiency IEQ measurement. This development of integration is also suitable for large-scale production and application.

    ●Extendibility:IBEM does not support sensor customization,and its functions are not flexible for different scenarios.Some other IEQ monitoring systems perform better. For example, OSBSS[21] is designed and constructed using open-source hardware and software based on the Arduino platform. All its sensors are customizable, which allows for more flexibility in costeffectively synchronizing a larger number of IEQ measurements.The IEQ system developed by Sun et al.[48]is another example with high-level extendibility. It consists of multiple modularized sensors, and users can freely choose different sensors by means of a simple plug-in.

    ●Data platform: This aspect is well presented in IBEM and in many other systems [20,23,24,47,50-52]. With the development of communication and web service technology, an increasing number studies are providing a software layer where end-users can access data,receive suggestions,and evaluate the performance of their built environment.

    ●Feedback and interaction: This aspect is an essential advantage of IBEM in comparison with the other tools and systems.Most systems can only show the measured IEQ performance to users and cannot ‘‘listen” to users; thus, they do not sufficiently build a pathway for information interaction between the occupants and their environment. However, IBEM presents real-time IEQ conditions to building occupants immediately and collects their subjective feedback at the same time.This feedback is essential for demand control, which can be used to achieve a high level of occupant satisfaction and low energy consumption. Furthermore, bidirectional data flow on IEQ creates new research opportunities and more value in the field of the built environment. For example, Zhuang et al.[53,54] found that interactive feedback transformed building occupants’ style of IEQ control from a habit-driven mode to a deliberate thinking mode and induced more positive behaviors toward energy conservation, such as setting thermostats with higher temperatures in summer.

    According to these comparison results,IBEM performs better on the integration and data platform level, especially in regard to feedback and interaction, but worse in terms of the diversity of sensors and extendibility.

    This study has other limitations that need to be improved in future works. Firstly, a scientific and simplified deployment scheme for IBEM has not been proposed. Although IBEM enables cost-effective built environment measurements,it is still necessary to deploy many onsite devices—a task that mainly relies on manual experience. Based on the measured big data from buildings with different scenarios, it is expected to identify the coupling relationships for IEQ data between different sample locations,which can reduce unnecessary devices. At that time, we will be able to achieve the whole-field monitoring of IEQ based on a limited number of devices and transform the IBEM deployment methodology from an experience-based model to a data-driven model. Secondly, IBEM is not automatically linked with the environmental control system,which limits its IEQ optimization application. We are still working on integrating the real-time IEQ monitoring records and occupant satisfaction ratings with the intelligent control system.

    6. Conclusions

    This study introduced an intelligent IEQ monitoring and feedback system (IBEM) and presented its field validation and several application cases. The IBEM hardware instrument integrates air temperature, RH, CO2, PM2.5, and illuminance sensors into a small device, significantly reducing the cost and improving deployment efficiency. The performance and accuracy of this integrated IEQ monitoring device have been tested through co-location experiments with reference sensors.The IBEM device strongly correlated with its counterparts, with slight deviation (R2>0.97 and slopes between 1.01 and 1.05). In terms of software design, IBEM can achieve wireless data transmission and cloud storage.More importantly, two types of graphical user interfaces (i.e., a web platform and a mobile interface)are built for data visualization and interactive feedback. Therefore, IBEM can continuously monitor IEQ parameters with a high spatiotemporal resolution,induce interactive feedback with building occupants,and realize the synchronous data collection of occupant satisfaction and objective environmental parameters at the same time and location.

    To date,IBEM has been widely applied in 131 buildings from 18 cities/areas in China,and an extensive IEQ database with a total of 1188 sample locations and more than 1.09 TB of data has been established. Furthermore, based on IBEM, we have conducted targeted IEQ diagnoses of individual buildings and explored the correlations between subjective and objective IEQ data in real-world scenarios.This work demonstrates the great value of IBEM in both industrial and academic research.

    Acknowledgments

    This study is supported by the China National Key Research and Development (R&D) Program (2018YFE0106100), the National Science Foundation for Distinguished Young Scholars of China(51825802),the Innovative Research Groups of the National Natural Science Foundation of China(51521005),the Strategic Research and Consulting Project of Chinese Academy of Engineering (2021-XY-3). The first author acknowledges the China Postdoctoral Science Foundation(2021M691789)and Shuimu Tsinghua Scholar Program (2020SM001).

    Appendix A. Supplementary data

    Supplementary data to this article can be found online at https://doi.org/10.1016/j.eng.2021.09.017.

    免费av毛片视频| 级片在线观看| 亚洲高清免费不卡视频| 免费高清视频大片| 天天躁夜夜躁狠狠久久av| 成年版毛片免费区| 久99久视频精品免费| 亚洲欧美成人综合另类久久久 | 日韩精品中文字幕看吧| 一本精品99久久精品77| 午夜爱爱视频在线播放| 色综合亚洲欧美另类图片| 人妻制服诱惑在线中文字幕| 天堂影院成人在线观看| 成年女人永久免费观看视频| 一区福利在线观看| 村上凉子中文字幕在线| 97碰自拍视频| 熟女电影av网| 综合色av麻豆| 亚洲av电影不卡..在线观看| 一进一出抽搐动态| 美女cb高潮喷水在线观看| 舔av片在线| 国产精品亚洲一级av第二区| 一级毛片aaaaaa免费看小| 99热全是精品| 久久午夜福利片| 女生性感内裤真人,穿戴方法视频| 色在线成人网| 日韩欧美在线乱码| 国产精华一区二区三区| 日本欧美国产在线视频| 国产私拍福利视频在线观看| 亚洲第一区二区三区不卡| 99热精品在线国产| 国产日本99.免费观看| 久久6这里有精品| 高清日韩中文字幕在线| ponron亚洲| 不卡视频在线观看欧美| 人妻丰满熟妇av一区二区三区| 欧美色视频一区免费| 天天躁日日操中文字幕| .国产精品久久| 男插女下体视频免费在线播放| 色综合亚洲欧美另类图片| 一个人看的www免费观看视频| 99热精品在线国产| 一本精品99久久精品77| 真实男女啪啪啪动态图| 国产aⅴ精品一区二区三区波| 欧美高清性xxxxhd video| 国产精品嫩草影院av在线观看| 国产精品爽爽va在线观看网站| 淫秽高清视频在线观看| 亚洲性夜色夜夜综合| 亚洲性夜色夜夜综合| 成人午夜高清在线视频| av在线播放精品| 精品一区二区免费观看| 亚洲第一区二区三区不卡| 亚洲美女搞黄在线观看 | 插逼视频在线观看| 九九在线视频观看精品| 国产爱豆传媒在线观看| 久久久午夜欧美精品| 搡老岳熟女国产| 精品一区二区三区人妻视频| 国产白丝娇喘喷水9色精品| 99久久九九国产精品国产免费| 伦理电影大哥的女人| 啦啦啦韩国在线观看视频| 国产在线精品亚洲第一网站| 99久久精品一区二区三区| 真人做人爱边吃奶动态| 91狼人影院| .国产精品久久| 人妻制服诱惑在线中文字幕| 国产人妻一区二区三区在| 国产亚洲91精品色在线| 天堂动漫精品| 亚洲av免费在线观看| 亚洲欧美成人综合另类久久久 | 亚洲熟妇熟女久久| 亚洲精品日韩av片在线观看| 插逼视频在线观看| 天堂av国产一区二区熟女人妻| 波多野结衣巨乳人妻| 极品教师在线视频| 午夜精品在线福利| 国产色婷婷99| 久99久视频精品免费| 日韩av在线大香蕉| 卡戴珊不雅视频在线播放| 久久九九热精品免费| 久久午夜亚洲精品久久| 午夜激情欧美在线| 色视频www国产| 中文字幕人妻熟人妻熟丝袜美| 97在线视频观看| 成人三级黄色视频| 99久久久亚洲精品蜜臀av| 2021天堂中文幕一二区在线观| 欧美日韩在线观看h| 卡戴珊不雅视频在线播放| 亚洲国产欧美人成| 香蕉av资源在线| 久久精品国产亚洲av香蕉五月| 成人二区视频| 亚洲中文字幕日韩| 成人高潮视频无遮挡免费网站| 99热这里只有精品一区| 国内精品宾馆在线| 99热只有精品国产| 看非洲黑人一级黄片| 国产乱人视频| 少妇的逼水好多| 日韩欧美精品免费久久| 免费人成在线观看视频色| 极品教师在线视频| 久久国内精品自在自线图片| 91午夜精品亚洲一区二区三区| av福利片在线观看| 欧美绝顶高潮抽搐喷水| 白带黄色成豆腐渣| 不卡视频在线观看欧美| 久久亚洲国产成人精品v| 伦精品一区二区三区| 91在线观看av| 日本三级黄在线观看| 最近最新中文字幕大全电影3| 校园春色视频在线观看| 成熟少妇高潮喷水视频| 久久精品国产99精品国产亚洲性色| 性欧美人与动物交配| 亚洲av熟女| 国产一区二区亚洲精品在线观看| 久久久精品94久久精品| 97在线视频观看| 波多野结衣高清作品| 久久精品国产清高在天天线| 国产男人的电影天堂91| 一进一出好大好爽视频| 搡女人真爽免费视频火全软件 | 国内精品美女久久久久久| 亚洲欧美日韩高清在线视频| 男人狂女人下面高潮的视频| 在线观看美女被高潮喷水网站| 黄色视频,在线免费观看| 97在线视频观看| 99热只有精品国产| 亚洲最大成人av| 最近视频中文字幕2019在线8| 一级毛片久久久久久久久女| 国产精品爽爽va在线观看网站| 亚洲精品色激情综合| 成人特级av手机在线观看| 日韩三级伦理在线观看| 免费不卡的大黄色大毛片视频在线观看 | 免费一级毛片在线播放高清视频| 亚洲三级黄色毛片| 亚洲图色成人| 淫妇啪啪啪对白视频| 男女那种视频在线观看| 国产在线精品亚洲第一网站| 国产 一区 欧美 日韩| 成人美女网站在线观看视频| 麻豆一二三区av精品| 国产aⅴ精品一区二区三区波| 日韩大尺度精品在线看网址| 久久久久免费精品人妻一区二区| 白带黄色成豆腐渣| 精品不卡国产一区二区三区| 91午夜精品亚洲一区二区三区| 午夜影院日韩av| 99热这里只有是精品在线观看| 精品久久国产蜜桃| 黑人高潮一二区| 3wmmmm亚洲av在线观看| 亚洲av.av天堂| 亚洲精品国产av成人精品 | 精品午夜福利视频在线观看一区| 99久久成人亚洲精品观看| 精品久久久噜噜| 亚洲最大成人中文| 熟女电影av网| 午夜福利在线观看免费完整高清在 | 亚洲国产精品成人久久小说 | 精品日产1卡2卡| 国产探花在线观看一区二区| 少妇高潮的动态图| 一进一出抽搐gif免费好疼| 国产三级在线视频| 人人妻人人澡欧美一区二区| 免费av毛片视频| 少妇的逼好多水| 久久韩国三级中文字幕| 51国产日韩欧美| 色尼玛亚洲综合影院| 看黄色毛片网站| 小说图片视频综合网站| 国产一区二区三区av在线 | 国产精品人妻久久久影院| 日韩强制内射视频| 亚洲aⅴ乱码一区二区在线播放| 国产精品久久久久久av不卡| 秋霞在线观看毛片| 日本一本二区三区精品| 看免费成人av毛片| 22中文网久久字幕| 男女做爰动态图高潮gif福利片| 听说在线观看完整版免费高清| 久久午夜亚洲精品久久| 国产精品伦人一区二区| 国产伦精品一区二区三区四那| 看十八女毛片水多多多| 91午夜精品亚洲一区二区三区| 此物有八面人人有两片| 久久久久久久久大av| 日日干狠狠操夜夜爽| 又爽又黄无遮挡网站| 国产成人a区在线观看| 精品福利观看| 欧美区成人在线视频| 精品久久久久久久久亚洲| av在线天堂中文字幕| 亚洲国产色片| 亚洲图色成人| 国内精品一区二区在线观看| 亚洲精品在线观看二区| 国产成人福利小说| 男插女下体视频免费在线播放| 久久精品国产亚洲av天美| 亚洲性久久影院| 国产乱人视频| 哪里可以看免费的av片| 天天躁日日操中文字幕| 久久久久性生活片| 天天一区二区日本电影三级| 级片在线观看| 啦啦啦观看免费观看视频高清| 国产精品乱码一区二三区的特点| 91午夜精品亚洲一区二区三区| 久久久久久久久久黄片| 男女视频在线观看网站免费| 麻豆乱淫一区二区| 欧美潮喷喷水| 精品福利观看| 亚洲精品日韩av片在线观看| 听说在线观看完整版免费高清| 18禁在线无遮挡免费观看视频 | 精品不卡国产一区二区三区| 一级a爱片免费观看的视频| 欧美精品国产亚洲| 午夜精品在线福利| 最近最新中文字幕大全电影3| 成人高潮视频无遮挡免费网站| 亚洲国产精品sss在线观看| 精品久久国产蜜桃| 18禁裸乳无遮挡免费网站照片| 亚洲av不卡在线观看| 一个人看视频在线观看www免费| 美女大奶头视频| 久久久久久久午夜电影| 蜜桃久久精品国产亚洲av| 中文资源天堂在线| 欧美+亚洲+日韩+国产| 久久久久久久久久黄片| 亚洲va在线va天堂va国产| 亚洲天堂国产精品一区在线| 少妇高潮的动态图| 亚洲国产高清在线一区二区三| 午夜影院日韩av| 亚洲精品国产成人久久av| 亚洲av熟女| 亚洲欧美日韩高清专用| 乱码一卡2卡4卡精品| 欧美三级亚洲精品| 亚洲精品日韩av片在线观看| 成人特级av手机在线观看| 色视频www国产| 免费av观看视频| 老熟妇仑乱视频hdxx| 久久久久久国产a免费观看| 三级毛片av免费| 日本在线视频免费播放| 两性午夜刺激爽爽歪歪视频在线观看| 成人三级黄色视频| 男女之事视频高清在线观看| 成年免费大片在线观看| 国产综合懂色| 不卡一级毛片| 免费高清视频大片| 99久国产av精品国产电影| 淫妇啪啪啪对白视频| 免费在线观看影片大全网站| 淫秽高清视频在线观看| 亚洲国产色片| 人人妻人人看人人澡| 国产精品无大码| 嫩草影院新地址| 午夜精品国产一区二区电影 | 国产不卡一卡二| 观看美女的网站| 国产v大片淫在线免费观看| 国产探花极品一区二区| 日本五十路高清| 少妇猛男粗大的猛烈进出视频 | 色哟哟·www| 国产精品久久视频播放| 亚洲av成人精品一区久久| 国产爱豆传媒在线观看| avwww免费| 久久6这里有精品| 狂野欧美白嫩少妇大欣赏| 久久久久久久久中文| av天堂在线播放| av在线播放精品| 日本黄色片子视频| 人妻制服诱惑在线中文字幕| 国产极品精品免费视频能看的| 波多野结衣高清作品| 在现免费观看毛片| 麻豆一二三区av精品| 日韩欧美精品v在线| 嫩草影院精品99| 免费看av在线观看网站| 大香蕉久久网| 色噜噜av男人的天堂激情| 亚洲高清免费不卡视频| 国产精品伦人一区二区| 波多野结衣巨乳人妻| 成人av一区二区三区在线看| 亚洲最大成人av| 国产精品久久久久久久久免| 亚洲av五月六月丁香网| av免费在线看不卡| 国产亚洲av嫩草精品影院| 中文字幕av在线有码专区| 91av网一区二区| 免费高清视频大片| 三级毛片av免费| 久久精品国产亚洲av涩爱 | 亚洲第一区二区三区不卡| 久久精品影院6| 久久久国产成人免费| 老司机午夜福利在线观看视频| 亚洲欧美精品自产自拍| 激情 狠狠 欧美| 亚洲精品乱码久久久v下载方式| 成年女人看的毛片在线观看| 国产国拍精品亚洲av在线观看| aaaaa片日本免费| 又黄又爽又免费观看的视频| 国产私拍福利视频在线观看| 亚洲成人久久爱视频| 十八禁国产超污无遮挡网站| 亚洲人成网站在线观看播放| 成人三级黄色视频| 俺也久久电影网| 成人永久免费在线观看视频| 丰满的人妻完整版| 午夜老司机福利剧场| 可以在线观看毛片的网站| 国产一区二区在线观看日韩| 色播亚洲综合网| 黄色欧美视频在线观看| 日本五十路高清| 久久久久国内视频| 91狼人影院| 男女做爰动态图高潮gif福利片| 国产欧美日韩一区二区精品| 午夜日韩欧美国产| 男女下面进入的视频免费午夜| 成人性生交大片免费视频hd| 黄色日韩在线| 色吧在线观看| 少妇熟女欧美另类| 伦理电影大哥的女人| 长腿黑丝高跟| 日本三级黄在线观看| 人人妻,人人澡人人爽秒播| 亚洲va在线va天堂va国产| 亚洲中文日韩欧美视频| 欧美bdsm另类| 最近2019中文字幕mv第一页| 尾随美女入室| 欧美bdsm另类| 亚洲欧美日韩高清专用| 黄色配什么色好看| 色吧在线观看| 51国产日韩欧美| 搞女人的毛片| 亚洲熟妇熟女久久| 一卡2卡三卡四卡精品乱码亚洲| 久久久久久九九精品二区国产| 久久久久久国产a免费观看| 特大巨黑吊av在线直播| 成人特级黄色片久久久久久久| 国产精品一区二区三区四区久久| 久久九九热精品免费| 亚洲人成网站在线播| 久久久久国产精品人妻aⅴ院| 日韩三级伦理在线观看| 给我免费播放毛片高清在线观看| 成人精品一区二区免费| 看非洲黑人一级黄片| 国产人妻一区二区三区在| 人妻制服诱惑在线中文字幕| 国产亚洲91精品色在线| 一进一出抽搐动态| 毛片一级片免费看久久久久| 日韩欧美国产在线观看| 给我免费播放毛片高清在线观看| av中文乱码字幕在线| 尾随美女入室| 自拍偷自拍亚洲精品老妇| 男人的好看免费观看在线视频| 国产成人a区在线观看| av国产免费在线观看| 亚洲欧美中文字幕日韩二区| 看十八女毛片水多多多| 日韩强制内射视频| 十八禁国产超污无遮挡网站| 日本色播在线视频| 国内精品宾馆在线| 大香蕉久久网| 国产一区二区三区在线臀色熟女| 精品人妻一区二区三区麻豆 | 亚洲精品粉嫩美女一区| 久久久久性生活片| h日本视频在线播放| 天堂√8在线中文| 国产v大片淫在线免费观看| 成人av一区二区三区在线看| 日韩av在线大香蕉| 久久久久久久久久久丰满| 寂寞人妻少妇视频99o| 丝袜美腿在线中文| av在线亚洲专区| 国产精品三级大全| 亚洲国产精品久久男人天堂| 日本-黄色视频高清免费观看| а√天堂www在线а√下载| 亚洲在线自拍视频| 国产精品无大码| 国产淫片久久久久久久久| 色综合色国产| 女生性感内裤真人,穿戴方法视频| 精品久久久久久成人av| 亚洲激情五月婷婷啪啪| 成人无遮挡网站| 大又大粗又爽又黄少妇毛片口| 18禁黄网站禁片免费观看直播| 简卡轻食公司| 欧美最新免费一区二区三区| 99九九线精品视频在线观看视频| 亚洲天堂国产精品一区在线| 91av网一区二区| 在现免费观看毛片| 又黄又爽又免费观看的视频| 精品久久国产蜜桃| 老女人水多毛片| 午夜影院日韩av| 中国美女看黄片| 国产成人freesex在线 | 一级毛片aaaaaa免费看小| 婷婷色综合大香蕉| 午夜福利视频1000在线观看| 国产美女午夜福利| 成年版毛片免费区| 99九九线精品视频在线观看视频| 精品国内亚洲2022精品成人| 国产精品一及| 亚洲欧美精品综合久久99| 大型黄色视频在线免费观看| 禁无遮挡网站| 亚洲欧美日韩东京热| 淫秽高清视频在线观看| 国产在视频线在精品| 欧美日韩在线观看h| 国产人妻一区二区三区在| 亚洲电影在线观看av| 午夜福利在线观看吧| 大香蕉久久网| 精品免费久久久久久久清纯| 人人妻人人看人人澡| 久久人人爽人人爽人人片va| 精品久久久久久成人av| 亚洲精品日韩av片在线观看| 最近的中文字幕免费完整| 日本-黄色视频高清免费观看| 欧美在线一区亚洲| 91在线观看av| 麻豆国产97在线/欧美| 尤物成人国产欧美一区二区三区| 人人妻人人澡欧美一区二区| 欧美色视频一区免费| 三级男女做爰猛烈吃奶摸视频| 日本a在线网址| 亚洲欧美成人精品一区二区| 亚洲国产欧洲综合997久久,| 久久精品国产鲁丝片午夜精品| 国产 一区精品| 非洲黑人性xxxx精品又粗又长| 一区二区三区高清视频在线| 欧美在线一区亚洲| 91在线观看av| 亚洲无线在线观看| 99精品在免费线老司机午夜| 99热只有精品国产| 别揉我奶头 嗯啊视频| 精品国产三级普通话版| 女人被狂操c到高潮| 免费看a级黄色片| 少妇人妻精品综合一区二区 | 国产aⅴ精品一区二区三区波| 看非洲黑人一级黄片| a级毛色黄片| av中文乱码字幕在线| 一本久久中文字幕| 国产伦精品一区二区三区四那| 国产精品av视频在线免费观看| 欧美成人精品欧美一级黄| 亚洲中文字幕日韩| 超碰av人人做人人爽久久| 日韩成人伦理影院| 我要看日韩黄色一级片| 成人精品一区二区免费| 国产男人的电影天堂91| 尤物成人国产欧美一区二区三区| eeuss影院久久| 午夜精品国产一区二区电影 | 十八禁网站免费在线| 男女那种视频在线观看| 高清日韩中文字幕在线| 99久国产av精品| 少妇人妻一区二区三区视频| 久久99热6这里只有精品| 日韩av不卡免费在线播放| 日韩亚洲欧美综合| 不卡一级毛片| 国产精品嫩草影院av在线观看| 亚洲国产高清在线一区二区三| 高清毛片免费观看视频网站| 亚洲av二区三区四区| 国产成人a∨麻豆精品| 免费av不卡在线播放| 两个人视频免费观看高清| 国产精品一区二区三区四区免费观看 | 嫩草影院精品99| 国产亚洲精品综合一区在线观看| 九九热线精品视视频播放| 国产精品电影一区二区三区| 成年女人永久免费观看视频| 国产激情偷乱视频一区二区| 日韩欧美三级三区| 国产色爽女视频免费观看| 国产高清视频在线观看网站| 淫妇啪啪啪对白视频| 免费电影在线观看免费观看| 国内久久婷婷六月综合欲色啪| 亚洲综合色惰| 亚洲久久久久久中文字幕| 亚洲自拍偷在线| aaaaa片日本免费| 男人舔奶头视频| 国产人妻一区二区三区在| 97碰自拍视频| 午夜爱爱视频在线播放| 精品一区二区三区人妻视频| 亚洲国产色片| 中文字幕av成人在线电影| 美女 人体艺术 gogo| 男人舔奶头视频| 女人被狂操c到高潮| 国产不卡一卡二| 高清毛片免费看| 国产精品,欧美在线| 中文在线观看免费www的网站| 日韩制服骚丝袜av| 亚洲天堂国产精品一区在线| 免费不卡的大黄色大毛片视频在线观看 | 在线观看午夜福利视频| 国产极品精品免费视频能看的| 可以在线观看的亚洲视频| 亚洲精品亚洲一区二区| 免费在线观看成人毛片| 久久人人精品亚洲av| 亚洲欧美精品综合久久99| 男人舔女人下体高潮全视频| 亚洲美女搞黄在线观看 | 成人二区视频| eeuss影院久久| 中文在线观看免费www的网站| 在线免费观看的www视频| 亚洲欧美日韩高清在线视频| АⅤ资源中文在线天堂| 国产色婷婷99| 综合色av麻豆| 特级一级黄色大片| 国产高清有码在线观看视频| 波野结衣二区三区在线| 禁无遮挡网站| 精品一区二区三区人妻视频| 热99re8久久精品国产| 亚洲精品日韩av片在线观看| 内地一区二区视频在线| 91麻豆精品激情在线观看国产| 免费观看精品视频网站| or卡值多少钱| 久久久久国产精品人妻aⅴ院| 久久午夜福利片| 精品一区二区三区人妻视频|